ADDENDUM #2
Masonry Chimney
Conversions
Follow the requirements and use
the equipment listed in the
illustration below to install this
appliance into an interior masonry
chimney.
Maximum vertical rise is 40'
Minimum vertical rise is 10'
See the chart on page 15 for
determining the correct restrictor
position.
NOTE: these restrictor positions
are based upon lab tests. The ideal
restrictor position may vary slightly.
The entire chimney system
must be air-tight. Make sure to
seal the flashing, clean-out,
and thimble connection, and to
inspect the chimney.
Co-Axial Straight
Lengths
#991 High Wind
Termination
#990 90° Elbow
Flashing (included in
#934 Masonry
Conversion Kit
Make sure the coaxial pipe
maintains a 1 clearance to any
combustible. The vent must be
sealed air-tight.
High-Temp.
Silicone
Connector with Cover
(included in #934 Masonry
Conversion Kit)
Interior Masonry Chimney
Standard Masonry Fireplace
Connector (included in #934
Masonry Conversion Kit)
secured and sealed to
block-off plate.
Flashing (included in
#934 Masonry
Conversion Kit)
#991 High Wind
Termination
The entire chimney system
must be air-tight. Seal the
connector cover and inspect
the chimney.
Make sure the coaxial pipe
maintains a 1 clearance to any
combustible. The vent must be
sealed air-tight.
High-Temp.
Silicone
4" Dia. Flex Line
(UL 1777 Gas Liner)
4" Dia. Flex Line
(UL 1777 Gas Liner)