Honeywell 301C User Manual
EC-FX
Modbus address * 256 + 1. For example an
EC-F9 at Modbus address 003 will appear as
769 or 0x0301.
object_type enumerated R C N
event_state enumerated R R N
if gas sensor fault Fault (1),
else normal (0)
object_name character string R N N
"EC-F9 GGGG AdXXX.GGGG" where GGGG
is the gas name and XXX is the Modbus
address. The gas name is often "NH3".
out_of_service boolean R R N
reliability enumerated O R N
As appropriate reports
no_fault_detected (0) or
unreliable other (7)
Fault is detected within 60 seconds
status_flags
in_alarm boolean R R N
if faulty "true" (1)
else "false" (0)
if faulty "true" (1)
else "false" (0)
out_of_service boolean R R N
Modbus address * 256 + 2. For example an
EC-F9 at Modbus address 003 will appear as
770 or 0x0302.
object_type enumerated R C N
event_state enumerated R C N
object_name character string R N N
"EC-F9 GGGG AdXXX.Amin" where GGGG is
the gas name and XXX is the Modbus
address. The gas name is often "NH3".
out_of_service boolean R C N
Gas threshold. Synchronization is
maintained with the 301C and the EC-F9.
Whichever value is written last is
distributed to the other two locations.
reliability enumerated O C N
status_flags
in_alarm boolean R C N
out_of_service boolean R C N
Modbus address * 256 + 3. For example an
EC-F9 at Modbus address 009 will appear as
771 or 0x0303.
object_type enumerated R C N
event_state enumerated R C N
object_name character string R N N
"EC-F9 GGGG AdXXX.Amax" where GGGG is
the gas name and XXX is the Modbus
address. The gas name is often "NH3".
out_of_service boolean R C N
Gas threshold. Synchronization is
maintained with the 301C and the EC-F9.
Whichever value is written last is
distributed to the other two locations.
reliability enumerated O C N
status_flags
in_alarm boolean R C N
out_of_service boolean R C N
Notes
1 -- 'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 -- 'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
90