Objects for 301EM continued
For rel1, Modbus address * 256 + 8,
For rel2, Modbus address * 256 + 9,
For rel3, Modbus address * 256 + 10,
For rel4, Modbus address * 256 + 11
object_type
enumerated R C N
event_state
enumerated
R C N
object_name character string R N N
"VA301EM GGGG AdXXX.RelL" where
GGGG
is the gas name, XXX is the Modbus
address and L
is the relay number.
out_of_service boolean R C N
present_value enumerated R R N
reliability enumerated 0 C N
active_text
character string O C N
status_flags
in_alarm boolean R C N
out_of_service boolean R R N
For Buzzer, Modbus address * 256 + 24,
For Out1, Modbus address * 256 + 25,
For Out2, Modbus address * 256 + 26,
For Out3, Modbus address * 256 + 27
object_type enumerated R C N
event_state enumerated R C N
object_name character string R N N
"VA301EM GGGG AdXXX.buzz"
"VA301EM GGGG AdXXX.out1"
"VA301EM GGGG AdXXX.out2"
"VA301EM GGGG AdXXX.out3"
where GGGG is the gas name, and XXX is
the Modbus address.
out_of_service boolean R C N
polarity enumerated R C N
present_value enumerated R R N
state of buzzer and three 24VDC outputs.
reliability enumerated 0 C N
status_flags
in_alarm boolean R C N
out_of_service boolean R C N
Notes
1 --
'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 -- 'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Binary Values (Four instances per 301EM, regardless of number of sensors.)