Honeywell 301C User Manual
Objects for 301EM
TxNumber * 256 + 1. The TxNumber is the
Modbus address plus the sensor number in
the 301EM. For example, sensor 2 on a
301EM at Modbus address 030 will appear
as 7937 or 0x1F01.
object_type enumerated
R C N
event_state
enumerated R R
N
object_name character string R N
N
"VA301EM
GGGG Ad
XXX.
GGGG" where
GGGG is the gas name and
XXX is the
Modbus address. Values for gas name
include "R11" and "NH3".
out_of_service boolean R
R N
reliability enumerated O
R N
As appropriate reports
no_fault_detected (0),
no_sensor (1), or
unreliable other (7)
Fault is detected within 60 seconds
status_flags
in_alarm boolean
R
R N
if faulty "true" (1)
else "false" (0)
out_of_service boolean
R R N
From 301EM, usually ppm (96)
For Amin, TxNumber * 256 + 2,
For Amax, TxNumber * 256 + 3,
For Bmin, TxNumber * 256 + 4,
For Bmax, TxNumber * 256 + 5,
For Cmin, TxNumber * 256 + 6,
For Cmax, TxNumber * 256 + 7
The TxNumber is the Modbus address plus
the sensor number in the 301EM.
object_type
enumerated R C N
event_state
enumerated R C N
object_name character string
R N N
"VA301EM GGGG AdXXX.LLLL" where GGGG
is the gas name, XXX is the
Modbus address plus the sensor number in
the 301EM and LLLL is a member of the set
{Amin, Amax, Bmin, Bmax, Cmin and
Cmax}.
out_of_service boolean R
C N
Writing alarm thresholds over BACnet not
supported.
reliability enumerated O C N
status_flags
in_alarm boolean R C N
out_of_service boolean R C
N
Notes
1 -- 'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 -- 'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
Gas (One instance per sensor on the 301EM.)
Analog Values (six instances for each sensor on the 301EM, up to 120).
Amin, Amax, Bmin, Bmax, Cmin, Cm