152 Temperature and Pressure page
Section 5: Startup and meter configuration Reference, Installation, and Operations Manual
June 2013 3-9000-743 Rev S
3. To configure Live Pressure, plus associated alarms, choose the setting listed in the table
below):
Table 5-18 Live Pressure Inputs
Daniel MeterLink
Display Name
Options and Guidelines
Is pressure gage or absolute?
• Gage (FALSE)
• Absolute (TRUE)
Atmospheric pressure
• Enter a value (KPaa or psia) within the range [30.0, 108.40 KPaa]
• This data point is only applicable when the input pressure unit is
specified as gage.
Live pressure, Min input
• Enter the pressure (KPag or psig if gage, KPaa or psia if absolute)
that corresponds to a 4 mA input signal. The pressure must be
within the range [0, 280e3 KPag or KPaa].
Live pressure, Max input
• Enter the pressure (KPag or psig if gage, KPaa or psia if absolute)
that corresponds to a 20 mA input signal. The pressure must be
within the range [0, 280e3 KPag or KPaa].
Pressure alarm, Low limit
• Enter a value (KPag or psig if gage, KPaa or psia if absolute) within
the range [0, 280e3 KPag or KPaa]. An alarm is generated when
the pressure is at or below this limit value.
Pressure alarm, High limit
• Enter a value (KPag or psig if gage, KPaa or psia if absolute) within
the range [0, 280e3 KPag or KPaa]. An alarm is generated when
the pressure is at or above this limit value.
Alarm Selection
• The Alarm selection determines what value to use while a live
input is in alarm. This value is common with the pressure Alarm
selection so when one is changed, the other will change to match.
• Choose Last good value or Fixed value