Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. YZE04811
INDOOR COIL MODEL NO. FC/MC60D + MV20D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1500 1600 1700
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57
65
T.C. 42.6 46.0 47.1 52.2 59.2 43.3 46.5 47.6 52.8 59.5 44.0 46.9 48.0 53.4 59.7
S.C. 43.5 41.8 35.9 36.2 29.0 44.2 42.9 37.0 37.3 29.6 44.9 44.0 38.0 38.4 30.2
K.W. 2.6 2.6 2.6 2.7 2.8 2.6 2.7 2.7 2.8 2.9 2.7 2.7 2.7 2.8 2.9
75
T.C. 41.4 44.1 45.0 50.0 56.4 42.1 44.5 45.4 50.6 56.7 42.7 44.9 45.9 51.1 57.0
S.C. 42.2 40.7 35.0 35.3 28.0 42.9 41.7 36.1 36.3 28.7 43.6 42.7 37.1 37.4 29.3
K.W. 2.9 3.0 3.0 3.1 3.2 3.0 3.0 3.0 3.1 3.2 3.0 3.1 3.1 3.2 3.3
85
T.C. 40.2 42.2 42.9 47.8 53.6 40.8 42.6 43.3 48.3 53.9 41.5 43.0 43.7 48.7 54.3
S.C. 41.0 39.6 34.1 34.3 27.1 41.6 40.6 35.2 35.4 27.7 42.2 41.5 36.2 36.4 28.3
K.W. 3.3 3.3 3.3 3.4 3.5 3.3 3.3 3.4 3.4 3.5 3.4 3.4 3.4 3.5 3.6
95
T.C. 39.0 40.2 40.8 45.6 50.8 39.6 40.7 41.2 46.0 51.2 40.2 41.1 41.6 46.3 51.5
S.C. 39.7 38.4 33.3 33.3 26.1 40.3 39.4 34.3 34.4 26.8 40.8 40.3 35.3 35.5 27.4
K.W. 3.6 3.7 3.7 3.7 3.8 3.7 3.7 3.7 3.8 3.9 3.7 3.7 3.7 3.8 3.9
105
T.C. 36.7 37.5 37.7 42.4 47.2 37.2 37.9 38.1 42.7 47.6 37.7 38.2 38.4 43.0 48.0
S.C. 37.3 36.4 31.4 32.1 25.2 37.8 37.1 32.4 33.1 25.7 38.2 37.8 33.3 34.1 26.3
K.W. 4.2 4.2 4.1 4.2 4.3 4.2 4.2 4.2 4.3 4.4 4.2 4.2 4.2 4.3 4.4
115
T.C. 34.5 34.9 34.7 39.3 43.6 34.9 35.2 35.1 39.5 44.1 35.3 35.5 35.4 39.8 44.5
S.C. 35.0 34.3 29.6 30.9 24.2 35.4 34.8 30.5 31.8 24.7 35.7 35.3 31.3 32.7 25.2
K.W. 4.6 4.6 4.6 4.7 4.8 4.7 4.7 4.7 4.8 4.8 4.7 4.7 4.7 4.8 4.9
125
T.C. 32.3 32.3 31.8 36.2 40.1 32.6 32.5 32.0 36.4 40.6 32.8 32.7 32.3 36.5 41.0
S.C. 32.7 32.3 27.9 29.6 23.3 32.9 32.6 28.6 30.5 23.7 33.2 32.8 29.3 31.4 24.1
K.W. 5.1 5.1 5.1 5.2 5.3 5.2 5.2 5.1 5.2 5.3 5.2 5.2 5.2 5.3 5.4
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
F*FV060 0.95 1.00 0.95
AV48 0.95 1.00 0.95
AV60 0.95 1.00 0.95
MV20D FC/MC60D 1.00 1.00 1.00
MV20D FC/MC62D 1.01 1.01 1.01
Variable Speed
Furnace
Coil
T.C. S.C. KW
P(C,V)9*D20 FC/MC/PC60D 1.02 0.98 1.02
P(C,V)9*D20 FC/MC62D 1.07 0.97 1.07
PV8*C20 FC/PC60C 1.02 0.98 1.02
P(C,V)9*C20 FC/PC60C 1.02 0.98 1.02
P(C,V)9*D20 HC60 1.02 0.98 1.02
PV8*C20 HC60 1.02 0.98 1.02
P(C,V)9*D20 HD60 1.02 0.98 1.02
P(C,V)9*D20 FC/MC62D 1.07 0.97 1.07
P(C,V)9*C20 UC60C 1.02 0.98 1.02
PV8*C20 UC60C 1.02 0.98 1.02
P(C,V)9*D20 UC60D 1.02 0.98 1.02