York Y34 Air Conditioner User Manual


 
246653-YTG-E-0108
30 Johnson Controls Unitary Products
TABLE 29: DRIVE ADJUSTMENT FOR POWER EXHAUST - 25 TON
5 HP MOTOR & 759 RPM DRIVE 7.5 HP MOTOR & 852 RPM DRIVE 10 HP MOTOR & 975 RPM DRIVE
%RPM
& CFM
REQD
PD
B
ROWNING
2B5V_ _
%RPM
& CFM
R
EQD
PD
B
ROWNING
2
B5V_ _
%RPM
& CFM
R
EQD PD
B
ROWNING
2
B5V_ _
100 (Std.) 4.9 46 92 5.1 48 93 5.9 56
104 5.1 48 96 5.3 50 97 6.1 58
109 5.3 50 100 (Std.) 5.5 52 100 (Std.) 6.3 60
113 5.5 52 104 5.7 54 103 6.5 62
117 5.7 54 108 5.9 56 107 6.7 64
122 5.9 56 112 6.1 58 110 6.9 66
TABLE 30: DRIVE ADJUSTMENT FOR POWER EXHAUST - 30 & 40 TON
7.5 HP MOTOR & 852 RPM DRIVE 10 HP MOTOR & 976 RPM DRIVE 15 HP MOTOR & 1069 RPM DRIVE
% RPM
& CFM
REQ’D
PD (
IN)
B
ROWNING
2B5V_ _
% RPM
& CFM
REQ’D
PD (IN)
B
ROWNING
2B5V_ _
% RPM
& CFM
REQ’D
PD (IN)
B
ROWNING
2B5V_ _
96.4 5.3 52 93.7 5.9 58 94.2 6.5 64
100.0 (Std.) 5.5 54 96.8 6.1 60 97.1 6.7 66
103.6 5.7 56 100.0 (Std.) 6.3 62 100.0 (Std.) 6.9 68
107.3 5.9 58 103.2 6.5 64 102.9 7.1 70
110.9 6.1 60 106.3 6.7 66 108.7 7.5 74
114.5 6.3 62 109.5 6.9 68 117.4 8.1 80