York Y34 Air Conditioner User Manual


 
246653-YTG-E-0108
10 Johnson Controls Unitary Products
* Unit Control Board with 3 heating outputs only, all other Unit Control Boards 2/1.
TABLE 1: GENERAL PHYSICAL DATA
UNIT SIZE 25 TON 30 TON 40 TON
U
NIT EER / IPLV
(S
TANDARD CAPACITY EVAPORATOR)
10.0 / 10.92 9.5 / 10.97 9.5 / 9.73
C
OMPRESSOR DATA
NUMBER/SIZE 2 x 12.5 Ton 3 x 10 Ton 4 x 10 Ton
T
YPE Scroll Scroll Scroll
U
NIT CAPACITY STEPS 50%, 100% 33%, 67%, 100% 25%, 50%, 75%, 100%
I
NDOOR FAN AND DRIVE
NUMBER / TYPE 1 / FC 1 / FC 1 / FC
D
IAMETER X WIDTH (INCHES) 22 x20 22 x 20 25 x 22
HP R
ANGE 7.5 - 20 10 - 25 10 - 25
CFM R
ANGE (FULL LOAD) 6,000 - 12,500 6,000 - 15,000 8,000 - 18,000
ESP R
ANGE 0.2” - 4.0” 0.2" - 4.0” 0.2" - 4.0"
E
XHAUST FAN
NUMBER/SIZE/TYPE 1/FC 2/FC 2/FC
HP R
ANGE (SINGLE MOTOR) 5 - 10 7.5 - 15 7.5 - 15
CFM 3,000 - 9,000 4,000 - 18,000 4,000 - 18,000
S
TANDARD EVAPORATOR COIL
SIZE (SQ. FT.) 26.0 26.0 30.4
R
OWS/FPI 3 / 13 3 / 16 4 / 13
H
IGH CAPACITY EVAPORATOR COIL
SIZE (SQ. FT.) 26.0 26.0 30.4
R
OWS/FPI 2/16 4 / 16 4 / 16
C
ONDENSER COIL
SIZE (SQ. FT.) 52.0 48.8 65.0
R
OWS/FPI 2/16 2 /16 2 /16
C
ONDENSER FANS
QUANTITY / DIAMETER (INCHES) 4 / 24 3 / 24 4 / 24
N
OMINAL CFM 4,600 6,800 6,800
M
OTOR HP 3 / 4 1.0 1.0
E
LECTRIC HEAT
K
W RANGE 40 - 108 40 - 108 40 - 108
40
KW 111
80
AND 108 KW / CAPACITY STEPS (CV/VAV) 2 / 1 2 / 1 2 / 1
N
ATURAL GAS HEAT
UNIT SIZE 25 TON 30 TON 40 TON
267 MBH C
APACITY STEPS (CV/VAV) 1 / 1 1 / 1 1 / 1
533 MBH C
APACITY STEPS (CV/VAV) 2 / 1 2 / 1 2 / 1
800 MBH C
APACITY STEPS (CV/VAV) --3 / 1*
267 MBH “M
ODULATING” CAPACITY STEPS (CV ONLY) 6 / 1 6 / 1 6 / 1
533 MBH “M
ODULATING” CAPACITY STEPS (CV ONLY) 12 / 2 12 / 2 12 / 2
800 MBH “M
ODULATING” CAPACITY STEPS (CV ONLY) --17 / 3
H
OT WATER COIL
SIZE (INCHES) 22.5” x 65” 22.5" X 65” 22.5" X 65”
C
APACITY 25 Ton 30 Ton 40 Ton
S
TEAM COIL
SIZE (INCHES) 21" X 65"
T
YPE Steam Coil
F
ILTERS 2" TA
N
UMBER / SIZE 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
F
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
ILTERS 2" PLEATED, 30%
N
UMBER / SIZE 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
F
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
ILTERS 65% RIGID W/ 2” TA PREFILTERS
NUMBER / SIZE 4 / 16 x 25 & 6 / 20 x 25 4 /16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
F
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
ILTERS 95% RIGID W/ 2” TA PREFILTERS
NUMBER / SIZE 4 ea. 16 x 25 / 6 ea. 20 x 25 4 ea. 16 x 25 / 6 ea. 20 x 25 4 ea. 16 x 25 / 6 ea. 20 x 25
F
ACE AREA (SQ. FT.) 30.4 30.4 30.4