York TCGD18 THRU 60 Air Conditioner User Manual


 
359315-YTG-B-0408
2 Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
request.
Physical and Electrical Data
MODEL
TCGD18
S41S1(H)
TCGD24
S41S1(H)
TCGD30
S41S1(H)
TCGD36
S41S1(H)
TCGD42
S41S1(H)
TCGD48
S41S1(H)
TCGD60
S41S1
Unit Supply Voltage 208-230V, 1φ, 60Hz
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 10.0 12.4 14.7 17.9 21.5 21.1 34.3
Max. Overcurrent Device Amps
2
15 20 25 30 35 35 60
Min. Overcurrent Device Amps
3
15 15 15 20 25 25 35
Compressor Type Rotary Recip Recip Recip Recip Recip Scroll
Compressor Amps
Rated Load 7.6 9.3 10.6 13.1 16.0 15.7 26.2
Locked Rotor 40.0 43.0 54.0 74 84 84 150
Crankcase Heater No No No No No No No
Fan Motor Amps Rated Load 0.5 0.8 1.4 1.5 1.5 1.5 1.5
Fan Diameter Inches 17.5 17.5 17.5 22 22 22 24
Fan Motor
Rated HP 1/12 1/8 1/4 1/4 1/4 1/4 1/4
Nominal RPM 1100 1075 1100 850 850 850 850
Nominal CFM 1400 1950 2050 3200 2950 2950 3600
Coil
Face Area Sq. Ft. 9.60 9.60 9.60 13.07 14.16 14.16 18.68
Rows Deep 1 1 1 1 1 1 1
Fin / Inches 23 23 23 23 23 23 23
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed) 5/8 3/4 3/4 3/4 7/8 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
3 - 3 3 - 13 3 - 14 4 - 9 4 - 5 4 - 9 5 - 6
Charge Per Foot, Oz. 0.58 0.62 0.62 0.62 0.67 0.67 0.67
Operating Weight Lbs. 97 129 131 145 173 173 195
Models with “H” on the end of the model number have a factory installed start kits.
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
B
C
A
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1.Including Fan Guard.
B C Liquid Vapor
18 28
23-1/2 23-1/2
3/8”
3/4”
24 28 23-1/2 23-1/2
30 28 23-1/2 23-1/2
36 28 29 29
42 30 29 29
7/8”48 30 29 29
60 32 33-5/8 33-5/8