York TCGD18 THRU 60 Air Conditioner User Manual


 
359315-YTG-B-0408
Johnson Controls Unitary Products 17
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD60S41S1(H)
INDOOR COIL MODEL NO. FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 55.8 63.8 62.1 65.2 71.9 60.3 65.7 62.8 66.7 69.8 64.8 67.5 63.5 68.2 67.8
S.C. 54.7 51.6 41.4 41.1 34.1 58.4 54.2 43.9 42.6 31.9 62.1 56.8 46.5 44.2 29.6
KW 3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.1 3.0 3.1 3.0 3.1 3.1
75
T.C. 56.9 61.1 58.9 62.7 69.7 59.2 63.0 59.9 64.3 67.9 61.4 64.9 61.0 65.9 66.0
S.C. 53.9 50.4 40.5 40.0 33.5 55.8 53.1 43.1 41.8 31.5 57.7 55.7 45.6 43.6 29.5
KW 3.4 3.5 3.5 3.5 3.6 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
85
T.C. 58.0 58.4 55.7 60.3 67.6 58.0 60.4 57.1 61.9 65.9 58.1 62.4 58.5 63.6 64.1
S.C. 53.2 49.3 39.7 39.0 32.9 53.3 52.0 42.2 41.0 31.2 53.4 54.7 44.8 42.9 29.4
KW 3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0
95
T.C. 59.1 55.7 52.5 56.9 65.5 56.9 57.8 54.3 57.0 63.9 54.7 59.8 56.0 61.2 62.2
S.C. 52.4 48.1 38.8 37.9 32.3 50.7 50.9 41.4 38.8 30.8 49.0 53.6 43.9 42.3 29.4
KW 4.3 4.3 4.3 4.4 4.5 4.3 4.3 4.3 4.4 4.4 4.3 4.3 4.3 4.4 4.4
105
T.C. 56.4 52.2 48.8 54.0 60.1 54.0 54.3 50.5 55.7 59.7 51.6 56.3 52.2 57.4 59.4
S.C. 49.7 45.9 37.5 36.5 29.7 47.9 48.3 40.0 38.7 29.4 46.2 50.6 42.5 40.9 29.0
KW 4.9 4.9 4.9 4.9 5.0 4.9 4.9 4.9 5.0 5.0 4.9 4.9 4.9 5.0 5.0
115
T.C. 53.8 48.8 45.2 50.2 54.8 51.2 50.9 46.8 51.9 55.7 48.7 53.0 48.5 53.6 56.6
S.C. 47.1 43.8 36.2 35.0 27.3 45.3 45.7 38.6 37.3 27.9 43.5 47.7 41.1 39.6 28.6
KW 5.5 5.4 5.4 5.5 5.6 5.5 5.5 5.4 5.5 5.6 5.4 5.5 5.4 5.5 5.6
125
T.C. 51.2 45.4 41.6 46.5 49.4 48.5 47.5 43.2 48.2 51.6 45.7 49.7 44.8 49.8 53.8
S.C. 44.5 41.7 34.9 33.6 24.9 42.6 43.2 37.3 35.9 26.5 40.7 44.7 39.7 38.3 28.2
KW 6.1 6.0 5.9 6.1 6.2 6.0 6.0 6.0 6.1 6.2 6.0 6.0 6.0 6.1 6.2
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
FC/MC62 1.00 1.00 1.00
HC60 1.00 1.00 1.00
UC60 1.00 1.00 1.00
AHP/SHP60 1.00 1.00 1.00
AV/SV60 1.00 1.01 1.00
MV20D FC/MC60D 1.00 1.01 1.00
MA20D FC/MC60D 1.00 1.00 1.00
MV20D FC/MC62D 1.00 1.01 1.00
MA20D FC/MC62D 1.00 1.00 1.00
F5FP060 1.00 1.00 1.00
F4FV060 1.00 1.01 1.00
Variable Speed
Furnace
Coil T.C. S.C. KW
PV8*C20 FC/PC/UC60C 1.00 1.00 1.00
P(C,V)9*C20 FC/PC/UC60C 1.00 1.00 1.00
P(C,V)9*D20 FC/MC/PC/UC60D 1.00 1.00 1.00
PV8*C20 FC/MC62D 1.00 1.00 1.00
P(C,V)9*C20 FC/MC62D 1.00 1.00 1.00
P(C,V)9*D20 FC/MC62D 1.00 1.00 1.00