York H*BE-F018 Air Conditioner User Manual


 
332018-BTG-D-0208
4 Unitary Products Group
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of
interconnecting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
FC/MC/PC48D3X 702 + 12 703 + 9*
FC/PC60C3X ––––703 + 13 703 + 6* 2C + 0*
FC/MC/PC60D3X ––––703 + 13 703 + 6* 2C + 0*
MC61D3X –––––703 + 13 2C + 0
FC/MC62D3X –––––703 + 13 2C + 0
HC30A3X 2A + 0––––––
HC36B3X 2A + 02A + 0––––
HC42C3X 702 + 9 703 + 6*
HC60D3X ––––703 + 13 703 + 6* 2C + 0*
HD24A3X –––––––
HD36B3X 2A + 0 2A + 0 702 + 5
HD48C3X ––––703 + 0* 703 + 0*
HD60D3X ––––––2C + 0*
UC24A3X 2A + 0––––––
UC24B3X 2A + 0––––––
UC30A3X 2A + 0––––––
UC30B3X 2A + 0––––––
UC36A3X ––2A + 0––––
UC36B3X ––2A + 0––––
UC36C3X ––2A + 0––––
UC42B3X 702 + 0
UC42C3X 702 + 0
UC48C3X 702 + 12 703 + 9*
UC48D3X 702 + 12 703 + 9*
UC60C3X ––––703 + 13 703 + 6* 2C + 0*
UC60D3X ––––703 + 13 703 + 6* 2C + 0*
AHP24B3X 2A + 0––––––
AHP30B3X 2A + 02A + 0––––
AHP42C3X 702 + 9
AHP/SHP48D3X ––––703 + 13 703 + 6*
AHP/SHP60D3X 702 + 17 703 + 13 703 + 6 2C + 0
AV24B3X 2A + 0––––––
AV36C3X 2A + 0 2A + 0 702 + 9
AV/SV48D3X ––––703 + 13 703 + 6
AV/SV60D3X ––––703 + 13 703 + 6 2C + 0
F*FP040 ––2A + 0––––
F4FV060H06T2C –––––703 + 6 0
FOOTNOTES:
1. A TXV kit must be used with these coils to obtain system performance.
2. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
3. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
4. If no TXV is listed, the indoor coil has the correct valve factory installed.
* Does not achieve 14 SEER with PSC furnaces. For ratings, see technical guide or visit www.aridirectory.org/ari/unitary.html
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase (Continued)
Outdoor Unit HABE-F018S HDBE-F024S HCBE-F030S HABE-F036S HBBE-F042S HBBE-F048S HCBE-F060S
Required TXV
1
1TVM2A1 1TVM2A1 1TVM2A1 1TVM702 1TVM703 1TVM703 1TVM2C1
Factory Charge, lbs-oz 5 - 9 6 - 0 8 - 2 9 - 14 14 - 15 15 - 5 16 - 5
Indoor Coil
2,3
TXV
4
+ Charge Adder, Oz