332018-BTG-D-0208
Unitary Products Group 11
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. HDBE-F024S
INDOOR COIL MODEL NO. FC/MC/PC35
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 600 800 1000
ID DB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 20.1 22.8 25.9 27.9 23.1 24.6 26.9 29.0 26.1 26.4 27.9 30.2 25.6 27.9 30.2
S.C. 19.9 17.8 16.4 12.9 22.8 21.5 18.9 14.6 25.7 25.2 21.5 16.4 21.0 21.5 16.4
K.W 1.2 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
75
T.C. 19.3 21.6 24.8 26.8 22.0 23.3 25.8 27.8 24.8 25.1 26.8 28.8 24.3 26.8 28.8
S.C. 19.1 17.4 15.8 12.5 21.8 20.8 18.1 14.1 24.5 24.2 20.4 15.6 20.6 20.4 15.6
K.W 1.3 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
85
T.C. 18.5 20.3 23.7 25.7 21.0 22.1 24.7 26.5 23.5 23.8 25.8 27.4 23.0 25.8 27.4
S.C. 18.3 16.9 15.3 12.1 20.7 20.0 17.3 13.5 23.2 23.2 19.4 14.9 20.1 19.4 14.9
K.W 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.6 1.5 1.5 1.5 1.6 1.5 1.5 1.6
95
T.C. 17.6 19.1 22.6 24.6 19.9 20.8 23.7 25.3 22.2 22.6 24.7 25.9 21.7 24.7 25.9
S.C. 17.4 16.4 14.7 11.6 19.7 19.3 16.5 12.9 22.0 22.2 18.3 14.1 19.7 18.3 14.1
K.W 1.6 1.6 1.6 1.7 1.6 1.6 1.7 1.7 1.6 1.6 1.7 1.7 1.6 1.7 1.7
105
T.C. 16.8 18.2 20.8 22.8 18.8 19.6 21.6 23.4 20.7 21.1 22.5 24.0 20.1 22.5 24.0
S.C. 16.7 16.2 14.0 11.0 18.6 18.5 16.0 12.3 20.6 20.9 18.0 13.5 18.7 18.0 13.5
K.W 1.7 1.7 1.8 1.8 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.8 1.8
115
T.C. 16.0 17.4 19.0 21.1 17.7 18.4 19.7 21.6 19.3 19.4 20.4 22.1 18.6 20.4 22.1
S.C. 15.9 16.0 13.4 10.4 17.6 17.6 15.5 11.7 19.3 19.4 17.7 12.9 17.7 17.7 12.9
K.W 1.8 1.8 1.9 1.9 1.8 1.8 1.9 1.9 1.9 1.9 1.9 2.0 1.9 1.9 2.0
125
T.C. 15.2 16.5 17.3 19.4 16.6 17.2 17.7 19.8 17.9 18.3 19.2 20.1 17.1 18.2 20.1
S.C. 15.2 14.7 12.7 9.9 16.6 16.6 15.0 11.1 17.0 18.0 17.3 12.3 16.8 17.3 12.3
K.W 1.9 1.9 2.0 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.1 2.0 2.0 2.1
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
AHP30 – 1.00 1.00 1.00
AV36 – 1.00 1.00 1.00
MA12B FC/MC35B 1.01 1.00 0.97
MV12B FC/MC35B 1.01 1.00 0.97
– FC/MC/PC/UC32B 1.00 1.00 1.00
– HC36 1.00 1.00 1.00
– HD36 1.00 1.00 1.00
Variable Speed
Furnace
Coil
T.C. S.C. KW
(F,L)L8V*A12 FC/MC/PC32A 1.01 1.00 0.97
FL9V*A12 FC/MC/PC32A 1.01 1.00 0.97
FL9(C,V)*B12 FC/MC/PC35B 1.01 1.00 0.97
FL9(C,V)*B12 HC36 1.01 1.00 0.97
FL8V*B12 HD36 1.01 1.00 0.97
FL9(C,V)*B12 HD36 1.01 1.00 0.97