York E*BD-(T Heat Pump User Manual


 
246819-BTG-H-0208
2 Unitary Products Group
All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
request.
Physical and Electrical Data - 1 Phase
MODEL
EABD-F018S EABD-F024S EABD-F030S EABD-F036S EABD-F042S EABD-F048S EABD-F060S
Unit Supply Voltage 208-230V, 1φ, 60Hz
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 9.9 15.0 16.9 19.8 25.0 32.7 37.8
Max. Overcurrent Device Amps
2
15 25 25 30 40 50 60
Min. Overcurrent Device Amps
3
15 20 20 20 30 35 40
Compressor Type
4
Recip Recip Recip Recip Recip
Scroll
D
Scroll
D
Compressor
Amps
Rated Load 7.5 10.7 12.4 14.6 18.8 25.0 29.1
Locked Rotor 41 44 60 78 78 115 150
Crankcase Heater Yes Yes Yes Yes Yes No No
Fan Motor Amps Rated Load 0.5 1.5 1.5 1.5 1.5 1.5 1.5
Fan Diameter Inches 22 22 22 22 22 24 24
Fan Motor
Rated HP 1/15 1/4 1/4 1/4 1/4 1/4 1/4
Nominal RPM 850 850 850 850 850 850 850
Nominal CFM 2,000 3,250 3,450 3,500 3,500 3,400 3,500
Coil
Face Area Sq. Ft. 15.72 18.34 20.96 23.58 23.58 24.00 27.00
Rows Deep1111122
Fin / Inches 22 22 22 22 22 18 18
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed) 3/4 3/4 7/8 7/8 7/8 7/8 1-1/8
Unit Charge (Lbs. - Oz.)
5
7 - 1 6 - 6 8 - 7 8 - 7 8 - 7 12 - 8 16 - 7
Charge Per Foot, Oz. 0.68 0.68 0.70 0.70 0.70 0.70 0.76
Operating Weight Lbs. 172 184 196 208 208 250 294
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. All scrolls listed with a superscript “D” are Danfoss scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
5. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
A
B
C
Unit
Model
Dimensions
(Inches)
Refrigerant
Connection
Service Valve Size
A
1
1. Including Fan Guard.
* Adapter fitting required for 1-1/8” line set.
B C Liquid Vapor
018 27 37 27
3/8”
3/4”
024 31 37 27
030 35 37 27
7/8”
036 39 37 27
042 39 37 27
048 34 43 32
060 38 43 32 7/8”*