York DY 048 Air Conditioner User Manual


 
343615-YTG-B-0308
Johnson Controls Unitary Products 23
060
(5.0)
208-1-60 28.8 145.0 45.0 2.3 7.6 10.0
None - - - 55.9 60
E05 4.0 1 19.2 55.9 60
E07 5.6 1 26.9 55.9 60
E10 8.0 1 38.5 70.1 80
E15 11.9 2 57.2 93.5 100
E20 15.9 2 76.4 117.6 125
E30 22.2 2 106.7 155.4 175
230-1-60 28.8 145.0 45.0 2.3 7.6 10.0
None - - - 55.9 60
E05 5.3 1 23.0 55.9 60
E07 7.5 1 32.6 61.1 70
E10 10.6 1 46.1 77.2 80
E15 15.9 2 69.1 104.8 110
E20 21.2 2 92.2 132.4 150
E30 29.6 2 128.7 176.2 200
208-3-60 17.3 123.0 27.0 2.3 7.6 10.0
None - - - 41.5 45
E05 4.0 1 11.1 41.5 45
E07 5.6 1 15.5 41.5 45
E10 8.0 1 22.2 49.8 50
E15 11.9 2 33.0 63.3 70
E20 15.9 2 44.1 77.2 80
E30 22.2 2 61.6 99.0 100
230-3-60 17.3 123.0 27.0 2.3 7.6 10.0
None - - - 41.5 45
E05 5.3 1 13.3 41.5 45
E07 7.5 1 18.8 44.6 45
E10 10.6 1 26.6 53.9 60
E15 15.9 2 39.9 69.8 70
E20 21.2 2 53.2 85.7 90
E30 29.6 2 74.3 111.0 125
460-3-60 9.6 70.0 15.0 1.3 7.6 5.0
None - - - 22.1 25
E07 6.8 1 8.5 22.1 25
E10 10.1 1 12.7 26.2 25
E15 13.6 2 17.1 31.4 30
E20 19.5 2 24.5 40.3 40
E30 28.8 2 36.1 54.3 60
575-3-60 7.4 53.0 11.5 1.3 7.6 4.0
None - - - 17.3 20
E10 10.6 1 10.6 21.5 20
E15 15.9 1 16.0 27.9 30
E20 21.2 2 21.3 34.3 35
E30 30.4 2 30.5 45.4 45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET (CONT)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps