York DY 048 Air Conditioner User Manual


 
343615-YTG-B-0308
Johnson Controls Unitary Products 13
TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63 77 84 77 84 81 85 79 84
12
57171727374757172
25
05758555666666061
50
05353515160605555
100
0 50 50 45 46 60 60 53 53
200
0 49 49 43 44 58 58 50 50
400
04949424359594747
800
0 49 49 48 48 54 54 47 47
DY060 / 5 Ton
Horizontal Ducted Inlet
84
0 845 1166 1188
0.
2 0.6 0.3 1.3
1.51 0.80
169
5 1100 2618 1323
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
0.6
7 0.50
Cooling
Operation
2
(dB)
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Octave Center Freq.
ID Blower
Only (dB)
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 13: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63 82 87 79 88 88 89 82 87
125 75 76 72 74 82 83 78 78
250 69 69 66 66 79 79 73 73
500 64 64 60 60 72 72 66 66
1000 59 60 55 56 68 68 61 61
2000 55 55 50 50 65 65 57 57
4000 58 58 52 52 68 68 60 60
8000 55 55 49 49 66 67 56 56
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Octave Center Freq.
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
0.6
1100
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
DY060 / 5 Ton
Horizontal Ducted Discharge
840 845 1166 1188
0.80
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Eq uipment .
0.50
0.3
2618
1.51
Cooling
Operation
2
(dB)
0.2
1695
0.67
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
1.3
1323