York DY 048 Air Conditioner User Manual


 
343615-YTG-B-0308
14 Johnson Controls Unitary Products
TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63 77 86 79 88 81 86 83 87
125 69 70 70 72 71 73 72 72
250 56 63 56 58 64 72 63 69
500 50 52 48 49 57 59 53 56
1000 48 51 44 45 57 58 49 52
2000 43 47 39 41 54 57 47 50
4000 47 49 40 41 55 61 47 52
8000 46 47 44 45 51 57 47 49
DY060 / 5 Ton
Vertical Ducted Inlet
834 840 1171 1194
0.2 0.6 0.2 1.3
1525 1019 2624 1256
0.61 0.44 1.43 0.83
Octave Center Freq.
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
2
(dB)
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Eq uipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
TABLE 15: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63 83 88 82 88 91 91 85 88
125 78 78 75 76 85 85 79 79
250 66 67 62 62 77 78 70 72
500 59 60 54 54 70 70 61 61
1000 57 58 51 51 68 68 57 58
2000 51 52 45 45 62 63 52 53
4000 54 54 47 47 65 66 55 56
8000 52 52 46 47 65 66 52 53
DY060 / 5 Ton
Vertical Ducted Discharge
834 840 1171 1194
0.2 0.6 0.2 1.3
1525 1019 2624 1256
0.61 0.44 1.43 0.83
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Octave Center Freq.
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
2
(dB)
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Eq uipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
Cooling
Operation
2
(dB)
ID Blower
Only (dB)