TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63 77 86 79 88 81 86 83 87
125 6970707271737272
250 5663565864726369
500 5052484957595356
1000 4851444557584952
2000 4347394154574750
4000 4749404155614752
8000 4647444551574749
DY060 / 5 Ton
Vertical Ducted Inlet
834 840 1171 1194
0.2 0.6 0.2 1.3
1525 1019 2624 1256
0.61 0.44 1.43 0.83
Octave Center Freq.
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
2
(dB)
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Eq uipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
TABLE 15: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
63 83 88 82 88 91 91 85 88
125 7878757685857979
250 6667626277787072
500 5960545470706161
1000 57 58 51 51 68 68 57 58
2000 51 52 45 45 62 63 52 53
4000 54 54 47 47 65 66 55 56
8000 52 52 46 47 65 66 52 53
DY060 / 5 Ton
Vertical Ducted Discharge
834 840 1171 1194
0.2 0.6 0.2 1.3
1525 1019 2624 1256
0.61 0.44 1.43 0.83
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
Octave Center Freq.
ID Blower
Only (dB)
Cooling
Operation
2
(dB)
ID Blower
Only (dB)
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
2
(dB)
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Eq uipment.
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
Cooling
Operation
2
(dB)
ID Blower
Only (dB)