York DR150 Air Conditioner User Manual


 
246721-YTG-C-0606
28 Unitary Products Group
NOTE: Electric heaters are rated at nominal voltage. Use
this table to determine the electric heat capacity for
heaters supplied at lower voltages.
TABLE 15: ELECTRICAL DATA DR150 W/O PWRD CONVENIENCE OUTLET
RLALRAFLA3 5 35353535
ea. ea. ea. HP HP HP HP HP HP HP HP HP HP
None -- -- 61.9 67.1 67.4 72.6 80 80 80 90
2TP04521825 13.5 37.5 61.9 67.1 67.4 73.8 80 80 80 90
2TP04522425 18.0 50.0 76.1 82.6 83.0 89.5 80 90 90 90
2TP04523625 25.5 70.8 102.1 108.6 109.0 115.5 110 110 110 125
2TP04525425 40.6 112.7 154.5 161.0 161.4 167.9 175 175 175 175
None -- -- 61.9 67.1 67.4 72.6 80 80 80 90
2TP04521825 18.0 43.3 67.8 74.3 74.6 81.1 80 80 80 90
2TP04522425 24.0 57.7 85.8 92.3 92.7 99.2 90 100 100 100
2TP04523625 34.0 81.8 115.9 122.4 122.7 129.2 125 125 125 150
2TP04525425 54.0 129.9 143.5 150.0 150.4 156.9 175 175 175 175
None -- -- 27.4 30.2 29.6 32.4 35 35 35 40
2TP04521846 18 22.6 33.7 37.2 36.4 39.9 35 40 40 40
2TP04522446 24 30.1 42.7 46.2 45.5 49 45 50 50 50
2TP04523646 34 42.7 57.7 61.2 60.5 64 60 70 70 70
2TP04525446 54 67.8 71.6 75.1 74.3 77.8 80 90 80 90
None -- -- 22.5 24.4 24.3 26.2 25 30 30 30
2TP04521858 18 18.1 26.8 29.2 29 31.4 30 30 30 35
2TP04522458 24 24.1 34 36.4 36.2 38.6 35 40 40 40
2TP04523658 34 34.1 46 48.4 48.3 50.6 50 50 50 60
2TP04525458 54 54.2 57.1 59.5 59.3 61.7 70 70 70 70
*
Voltage
Compressors
OD Fan
Motors
Supply Blower
Motor FLA
Pwr Exh
Motor
Pwr
Conv
Outlet
Electric Heater
Model No.
Actual
KW
Heater
Amps
Min. Circuit
Ampacity
(Amps)
MCA w/Power
Exhaust
(Amps)
Max Fuse* Size
(Amps)
Max Fuse Size
w/Power
Exhaust
(Amps)
FLA FLA
208
20.0 146.0 1.5 10.9 16.1 5.5 0.0
230
20.0 146.0 1.5 10.9 16.1 5.5 0.0
460
8.4 73.0 0.8 5.3 8.1 2.2 0.0
575
7.1 60.0 0.6 4.1 6.0 1.8 0.0
Maximum HACR breaker of the same AMP size is applicable.
TABLE 16: ELECTRICAL DATA DR150 W/PWRD CONVENIENCE OUTLET
RLALRAFLA3 5 35353535
ea. ea. ea. HP HP HP HP HP HP HP HP HP HP
None -- -- 71.9 77.1 77.4 82.6 90 90 90 100
2TP04521825 13.5 37.5 73.0 79.5 79.8 86.3 90 90 90 100
2TP04522425 18.0 50.0 88.6 95.1 95.5 102.0 90 100 100 110
2TP04523625 25.5 70.8 114.6 121.1 121.5 128.0 125 125 125 150
2TP04525425 40.6 112.7 167.0 173.5 173.9 180.4 175 175 175 200
None -- -- 71.9 77.1 77.4 82.6 90 90 90 100
2TP04521825 18.0 43.3 80.3 86.8 87.1 93.6 90 90 90 100
2TP04522425 24.0 57.7 98.3 104.8 105.2 111.7 100 110 110 125
2TP04523625 34.0 81.8 128.4 134.9 135.2 141.7 150 150 150 150
2TP04525425 54.0 129.9 156.0 162.5 162.9 169.4 175 175 175 175
None -- -- 32.4 35.2 34.6 37.4 40 40 40 45
2TP04521846 18 22.6 39.9 43.4 42.7 46.2 40 45 45 50
2TP04522446 24 30.1 49 52.5 51.7 55.2 50 60 60 60
2TP04523646 34 42.7 64 67.5 66.7 70.2 70 70 70 80
2TP04525446 54 67.8 77.8 81.3 80.6 84.1 90 90 90 90
None -- -- 26.5 28.4 28.3 30.2 30 35 35 35
2TP04521858 18 18.1 31.8 34.2 34 36.4 35 35 35 40
2TP04522458 24 24.1 39 41.4 41.2 43.6 40 45 45 45
2TP04523658 34 34.1 51 53.4 53.3 55.6 60 60 60 60
2TP04525458 54 54.2 62.1 64.5 64.3 66.7 70 70 70 70
*
Voltage
Compressors
OD Fan
Motors
Supply Blower
Motor FLA
Pwr Exh
Motor
Pwr
Conv
Outlet
Electric Heater
Model No.
Actual
KW
Heater
Amps
Min. Circuit
Ampacity
(Amps)
MCA w/Power
Exhaust
(Amps)
Max Fuse* Size
(Amps)
Max Fuse Size
w/Power
Exhaust
(Amps)
FLA FLA
208
20.0 146.0 1.5 10.9 16.1 5.5 10.0
230
20.0 146.0 1.5 10.9 16.1 5.5 10.0
5.0
460
8.4 73.0 0.8
0.6
5.3 8.1 2.2
Maximum HACR breaker of the same AMP size is applicable.
4.1 6.0 1.8 4.0
575
7.1 60.0
TABLE 17: ELECTRIC HEAT MULTIPLIERS
VOLTAGE
kW Cap. Multiplier
NOMINAL RATING
240
208 0.75
230 0.92
480
460 0.92
600
575 0.92