York DM 240 Air Conditioner User Manual


 
262259-YTG-B-0107
24 Unitary Products Group
NOTE 1: HACR Type per NEC.
TABLE 16: DM 180, 240 ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET
MODEL
(TON-
NAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW STAGES AMPS
180
(15)
208 19.2 124 4.5 14.0 0.0
None 0.0 - - 85.4 100
E18 13.5 1 37.5 85.4 100
E36 27.0 2 75.1 111.2 125
E54 40.6 2 112.6 158.4 175
E72 54.1 2 150.1 167.7 200
230 19.2 124 4.3 14.0 0.0
None 0.0 - - 85.0 100
E18 18.0 1 43.3 85.0 100
E36 36.0 2 86.6 125.8 150
E54 54.0 2 129.9 147.4 175
E72 72.0 2 173.2 190.7 225
460 9.6 62 2.2 7.0 0.0
None 0.0 - - 42.6 50
E18 18.0 1 21.7 42.6 50
E36 36.0 2 43.3 62.9 70
E54 54.0 2 65.0 73.7 90
E72 72.0 2 86.6 95.4 110
575 7.7 50 1.7 5.3 0.0
None 0.0 - - 33.7 40
E18 18.0 1 17.3 33.7 40
E36 36.0 2 34.6 49.9 50
E54 54.0 2 52.0 58.6 70
E72 72.0 2 69.3 75.9 90
240
(20)
208 19.2 124 4.5 19.6 0.0
None 0.0 - - 110.3 125
E18 13.5 1 37.5 110.3 125
E36 27.0 2 75.1 118.2 125
E54 40.6 2 112.6 165.4 175
E72 54.1 2 150.1 174.7 200
230 19.2 124 4.3 19.6 0.0
None 0.0 - - 109.9 125
E18 18.0 1 43.3 109.9 125
E36 36.0 2 86.6 132.8 150
E54 54.0 2 129.9 154.4 175
E72 72.0 2 173.2 197.7 225
460 9.6 62 2.2 9.8 0.0
None 0.0 - - 55.1 60
E18 18.0 1 21.7 55.1 60
E36 36.0 2 43.3 66.4 70
E54 54.0 2 65.0 77.2 90
E72 72.0 2 86.6 98.6 110
575 7.7 50 1.7 8.2 0.0
None 0.0 - - 44.5 50
E18 18.0 1 17.3 44.5 50
E36 36.0 2 34.6 53.6 60
E54 54.0 2 52.0 62.2 70
E72 72.0 2 69.3 79.5 90