York DJ 180 Air Conditioner User Manual


 
261660-YTG-C-0707
Unitary Products Group 27
NOTE 1: HACR Type per NEC.
TABLE 20: DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET (CONTINUED)
MODEL
(TON-
NAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
STAGES AMPS
240
(20)
208 33.6 225 3.7 20.0 10.0
None 0.0 ~ ~ 120.4 150
E18 13.5 1 37.5 120.4 150
E36 27.0 2 75.1 131.2 150
E54 40.6 2 112.6 178.4 200
E72 54.1 2 150.1 187.7 200
230 33.6 225 3.7 20.0 10.0
None 0.0 ~ ~ 120.4 150
E18 18.0 1 43.3 120.4 150
E36 36.0 2 86.6 145.8 150
E54 54.0 2 129.9 167.4 175
E72 72.0 2 173.2 210.7 225
460 17.3 114 1.9 10.0 5.0
None 0.0 ~ ~ 61.5 70
E18 18.0 1 21.7 61.5 70
E36 36.0 2 43.3 72.9 80
E54 54.0 2 65.0 83.7 90
E72 72.0 2 86.6 105.4 110
575 13.5 80 1.5 8.2 4.0
None 0.0 ~ ~ 48.6 60
E18 18.0 1 17.3 48.6 60
E36 36.0 2 34.6 58.6 60
E54 54.0 2 52.0 67.2 70
E72 72.0 2 69.3 84.5 90
300
(25)
208 47.1 245 3.7 38.6 10.0
None 0.0 ~ ~ 169.4 200
E18 13.5 1 37.5 169.4 200
E36 27.0 2 75.1 169.4 200
E54 40.6 2 112.6 201.6 225
E72 54.1 2 150.1 210.9 225
230 47.1 245 3.7 38.6 10.0
None 0.0 ~ ~ 169.4 200
E18 18.0 1 43.3 169.4 200
E36 36.0 2 86.6 169.4 200
E54 54.0 2 129.9 190.7 225
E72 72.0 2 173.2 234.0 250
460 19.6 125 1.9 19.3 5.0
None 0.0 ~ ~ 76.0 90
E18 18.0 1 21.7 76.0 90
E36 36.0 2 43.3 84.5 90
E54 54.0 2 65.0 95.3 110
E72 72.0 2 86.6 117.0 125
575 15.8 100 1.5 15.4 4.0
None 0.0 ~ ~ 61.0 70
E18 18.0 1 17.3 61.0 70
E36 36.0 2 34.6 67.6 70
E54 54.0 2 52.0 76.2 90
E72 72.0 2 69.3 93.5 100