York DF 072 Air Conditioner User Manual


 
254599-YTG-C-0807
14 Unitary Products Group
TABLE 15: DF PHYSICAL DATA
MODELS
DF
072
EVAPORATOR
BLOWER
Centrifugal Blower (Dia. x Wd. in.) 12 X 10
Fan Motor HP (Direct Drive) 1
Fan Motor HP (Belt Drive) 1 1/2
EVAPORATOR
COIL
Rows Deep 4
Fins Per Inch 13
Face Area (Sq. Ft.) 5.1
CONDENSER
FANS
Propeller Dia. (in.) 24
Fan Motor Hp 1/2
Nom. CFM 4200
CONDENSER
COILS
Rows Deep 2
Fins Per Inch 18
Face Area (Sq. Ft.) 17.1
COMPRESSOR
(Qty. Per Unit)
Recip Type 1
AIR
FILTERS
Quantity Per Unit (15” X 20” X 1” or 2“) 2
Quantity Per Unit (14” X 25” X 1” or 2“) 1
Total Face Area (sq. ft.) 6.3
CHARGE
Refrigerant 22
(lbs./oz.)
11/10
TABLE 16: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
208
208 0.75
240
230 0.92
480
460 0.92
600
575 0.92
TABLE 17: VOLTAGE LIMITATIONS
1
1. Utilization Range “A” in accordance with ARI Standard
110.
POWER SUPPLY
VOLTAGE
MIN. MAX.
208/230-3-60
187 252
460-3-60
432 504
575-3-60
540 630