York DF 072 Air Conditioner User Manual


 
254599-YTG-C-0807
Unitary Products Group 13
TABLE 13: ELECTRICAL DATA - DF072 BELT DRIVE W/POWERED CONV. OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
ELECTRIC HEATER
MODEL NO.
HEATER
KW
HEATER
AMPS
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
DF072
(6.0)
208-3-60 20.7 156.0 2.3 5.2 10.0
None - - 43.4 60
2CE04510525
2
4 11.1 43.4 60
2CE04510725
2
5.6 15.5 43.4 60
2CE04511025 8 22.2 46.8 60
2CE04511525 11.9 33.0 60.3 70
2CE04512025 15.9 44.1 74.2 80
2CE04513025 22.2 61.6 96 100
230-3-60 20.7 156.0 2.3 5.2 10.0
None - - 43.4 60
2CE04510525
2
5.3 12.7 43.4 60
2CE04510725
2
7.5 18.0 43.4 60
2CE04511025 10.6 25.5 50.9 60
2CE04511525 15.9 38.2 66.8 70
2CE04512025 21.2 51.0 82.7 90
2CE04513025 29.6 71.2 108 110
460-3-60 10.0 75.0 1.3 2.6 5.0
None - - 21.4 30
2CE04510746
2
6.8 8.2 21.4 30
2CE04511046
2
10.1 12.1 24.7 30
2CE04511546
2
13.6 16.4 29.9 30
2CE04512046
2
19.5 23.5 38.8 40
2CE04513046
2
28.8 34.6 52.8 60
575-3-60 8.2 54.0 1.3 2.0 4.0
None - - 17.3 25
2CE04511058 10.6 10.2 20.2 25
2CE04511558 15.9 15.3 26.6 30
2CE04512058 21.2 20.4 33 35
2CE04513058 30.4 29.3 44.1 45
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
TABLE 14: ELECTRICAL DATA - DF072 DIRECT DRIVE W/POWERED CONV. OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
ELECTRIC HEATER
MODEL NO.
HEATER
KW
HEATER
AMPS
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
DF072
(6.0)
208-3-60 20.7 156.0 2.3 10.6 10.0
None - - 48.8 60
2CE04510525
2
4.0 11.1 48.8 60
2CE04510725
2
5.6 15.5 48.8 60
2CE04511025 8.0 22.2 53.5 60
2CE04511525 11.9 33.0 67.0 70
2CE04512025 15.9 44.1 80.9 90
2CE04513025 22.2 61.6 102.8 110
230-3-60 20.7 156.0 2.3 10.6 10.0
None - - 48.8 60
2CE04510525
2
5.3 12.7 48.8 60
2CE04510725
2
7.5 18.0 48.8 60
2CE04511025 10.6 25.5 57.6 60
2CE04511525 15.9 38.2 73.6 80
2CE04512025 21.2 51.0 89.5 90
2CE04513025 29.6 71.2 114.8 125
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.