York CU060 Air Conditioner User Manual


 
036-21217-001-B-1203
6 Unitary Products Group
NOTE: Cooling performance is rated at 80F dry bulb 67F wet bulb entering air temperature, CFM listed, 85F entering
95F leaving water temperature, and water flow rate listed. Gross capacity does not include the effect of evapora
-
tor fan motor heat.
TABLE 3: GENERAL DATA CU 300 25 TON VERTICAL MODELS
Model CU300
Nominal Cooling(Ton) 25
Cooling Performance
Gross Cooling Capacity(Btuh) 322000
Design CFM 10000
EER 11.5
Compressor-Type Scroll
Number Used 3
Evaporator Coil-Type Copper Tubes, Aluminum Fins
Face Area(sq ft) 19.79
Rows/FPI 4/12
Condenser-Type Coaxial
Number Used/Tons Capacity 3/7.5
Nominal Water flow rate (gpm) 78
Unit Water Connection Size 2 in FPT
Evaporator Fan-Type Centrifugal, Forward Curved
Number Used 2
Diameter x Width (in) 15x11
Drive Adjustable Belt
Motor HP (Standard/Oversize) 7.5/10
Filters
Number Used-Size(in) 8-20x20x2
Condensate Drain Connection 3/4FPT
Weight
Shipping 1825