York CU060 Air Conditioner User Manual


 
036-21217-001-B-1203
Unitary Products Group 5
NOTE: Cooling performance is rated at 80F dry bulb 67F wet bulb entering air temperature, CFM listed, 85F entering
95F leaving water temperature, and water flow rate listed. Gross capacity does not include the effect of evapora
-
tor fan motor heat.
TABLE 2: GENERAL DATA CU 5-20 TON VERTICAL MODELS
Model CU060A CU096A CU120A CU180A CU240A
Nominal Cooling(Ton) 5 8 10 15 20
Cooling Performance
Gross Cooling Capacity(Btuh) 63300 100600 127800 188600 246800
Design CFM 2000 3200 4000 6000 8000
EER 12.5 13.2 12.5 12.0 11.5
Compressor-Type Scroll
Number Used 1 2 2 2 2
Evaporator Coil-Type Copper Tubes, Aluminum Fins
Face Area(sq ft) 5.00 9.37 10.50 15.11 19.00
Rows/FPI 3/12 3/12 3/13 3/12 3/14
Condenser-Type Coaxial
Number Used/Tons Capacity 1/5 2/4 2/5 2/7.5 2/10
Nominal Water flow rate (gpm) 15 24 30 45 60
Unit Water Connection Size 1" FPT 1-1/4" FPT 1-1/4" FPT 1-1/2" FPT 2" FPT
Evaporator Fan-Type Centrifugal, Forward Curved
Number Used 1 1 1 2 2
Diameter x Width (in) 12x9 15x12 15x12 15x9 15x11
Drive Adjustable Belt
Motor HP (Standard/Oversize) 1/1.5 1.5/2 2/3 3/5 5/7.5
Filters
Number Used-Size(in) 2-20x16 4-14x25x2 6-14x20x2 2-16x20x2
4-16x25x2
6-20x25x2
Condensate Drain Connection 3/4FPT
Weight
Shipping 625 815 975 1350 1525