NOTE: Cooling performance is rated at 80F dry bulb 67F wet bulb entering air temperature, CFM listed, 85F entering
95F leaving water temperature, and water flow rate listed. Gross capacity does not include the effect of evapora
-
tor fan motor heat.
TABLE 1: GENERAL DATA - CH060-120 5-10 TON HORIZONTAL MODELS
Model CH060 CH096 CH120
Nominal Cooling(Ton) 5 8 10
Cooling Performance
Gross Cooling Capacity(Btuh) 64100 101800 126000
Design CFM 2000 3200 4000
EER 13.3 13.4 12.0
Compressor-Type Scroll
Number Used 1 2 2
Evaporator Coil-Type Copper Tubes, Aluminum Fins
Face Area(sq ft) 5.28 9.17 9.17
Rows/FPI 3/13 3/13 3/13
Condenser-Type Coaxial
Number Used/Tons Capacity 1/5 2/4 2/5
Nominal Water flow rate (gpm) 15 24 30
Condenser Water Connections 1" FPT 1-1/4" FPT 1-1/4" FPT
Evaporator Fan-Type Centrifugal, Forward Curved
Number Used 1 2 2
Diameter x Width (in) 10x10 10x8 10x8
Drive Adjustable Belt
Motor HP (Standard/Oversize) 1/NA 1.5/2 2/3
Filters
Number Used-Size(in) 2-20x20x2 2-20x25x2
1-20x20x2
2-20x25x2
1-20x20x2
Condensate Drain Connection 3/4FPT
Weight 460 710 760