York BHP024 Air Conditioner User Manual


 
036-21528-007-A-1205
Unitary Products Group 17
TABLE 17: ELECTRIC DATA (BASIC UNIT)
Model
BHP
Power
Supply
Voltage
Limitations
1
Compressor OD Fan
Motor
FLA
Supply Air
Blower
Motor
FLA
MCA
(Amps)
Max. Fuse
Size
(Amps)
2
Max HACR
Breaker
Size
(Amps)
Unit Power
Factor
Transformer
Size
(VA)
Min. Max. RLA LRA
024 208/230-1-60 187 253 9.3 57.0 1.1 5.0 17.7 25 25 0.96 40
030
208/230-1-60 187 253 15.0 72.5 1.1 5.0 24.9 30 30 0.96 40
208/230-3-60 187 253 10.0 63.0 1.1 5.0 18.6 25 25 0.96 75
460-3-60 414 504 5.0 31.0 0.6 5.0 11.9 15 15 0.96 75
036
208/230-1-60 187 253 17.2 94.0 1.1 7.3 29.9 35 35 0.96 40
208/230-3-60 187 253 11.4 78.0 1.1 7.3 22.7 30 30 0.96 75
460-3-60 414 504 5.7 40.0 0.6 7.3 15.4 20 20 0.96 75
575-3-60 518 630 4.7 31 0.6 6.8 12.7 20 20 0.96 75
042
208/230-1-60 187 253 20.0 104.0 1.1 7.3 33.4 40 40 0.96 40
208/230-3-60 187 253 13.9 88.0 1.1 7.3 25.8 30 30 0.96 75
460-3-60 414 504 6.4 44.0 0.6 7.3 16.1 20 20 0.96 75
575-3-60 518 630 5.4 34 0.6 6.8 13.4 20 20 0.96 75
048
208/230-1-60 187 253 23.4 126.0 1.5 7.3 38.1 45 45 0.96 40
208/230-3-60 187 253 13.0 93.0 1.5 7.3 25.1 30 30 0.96 75
460-3-60 414 504 6.4 46.5 0.8 7.3 16.3 20 20 0.96 75
575-3-60 518 630 5.1 37.2 0.6 6.8 13.8 20 20 0.96 75
060
208/230-1-60 187 253 25 150 2.3 9.1 42.7 50 50 0.96 40
208/230-3-60 187 253 17.3 130 2.3 9.1 33.0 40 40 0.96 75
460-3-60 414 504 8.4 70 1.3 9.1 21.1 25 25 0.96 75
575-3-60 540 630 7 53 1.1 9.1 19 25 25 0.96 75
1.
Rated in accordance with ARI Standard 110, utilization range “A”.
2.
Dual Element, Time Delay Type.
ELECTRIC HEAT
CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE KW CAP. MULTIPLIER
240
208
230
0.75
0.92
480 460 0.92
600 575 0.92