York BHP024 Air Conditioner User Manual


 
036-21528-007-A-1205
Unitary Products Group 15
NOTE: Above data includes allowances for a dry indoor coil and no filters. For additional pressure drops, refer to the “Additional Static Pressure
Resistance” table.
TABLE 15: SIDE & BOTTOM SUPPLY AIR BLOWER PERFORMANCE (208/230/460 VOLT
1
)
MODEL NO.
BHP
MOTOR SPEED
SETTING
UNIT
AIRFLOW
EXTERNAL STATIC PRESSURE - IWG
0.15 0.30 0.50 0.70 0.90
WATTS
B1HP024 Cooling TB2-A, Heating TB2-A, Electric Heat 800 CFM 91 125 161 206 240
B1HP024 Cooling TB2-B, Heating TB2-B 900 CFM 118 148 199 243 285
B1HP030 Cooling TB2-A, Heating TB2-A, Electric Heat 1000 CFM 280 321 389 449 500
B1HP030 Cooling TB2-B, Heating TB2-B 1125 CFM 356 413 490 557 620
B1HP036 Cooling TB2-A, Heating TB2-A 1050 CFM 209 261 319 372 438
B1HP036 Cooling TB2-B, Heating TB2-B, Electric Heat 1200 CFM 273 324 392 480 541
B1HP042 Electric Heat 1225 CFM 306 341 412 494 577
B1HP042 Cooling TB2-A, Heating TB2-A 1300 CFM 338 395 470 551 640
B1HP042 Cooling TB2-B, Heating TB2-B 1400 CFM 393 466 544 642 734
B1HP048 Heating TB2-A 1400 CFM 377 427 504 597 683
B1HP048 Cooling TB2-A 1500 CFM 455 516 601 703 788
B1HP048 Cooling TB2-B, Heating TB2-B, Electric Heat 1600 CFM 530 608 707 800 873
B1HP060 Cooling TB2-A 1600 CFM 385 478 489 596 703
B1HP060 Heating TB2-A 1900 CFM 400 493 593 700 807
B1HP060 Cooling TB2-B 2000 CFM 590 717 833 940 1047
1.
All units are factory set to TB2-A.
TABLE 16: ADDITIONAL STATIC RESISTANCE
DESCRIPTION
RESISTANCE, IWG
CFM
500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000
Wet Indoor Coil 0.01 0.01 0.01 0.02 0.01 0.02 0.03 0.04 0.04 0.03 0.04 0.04 0.05 0.05 0.06 0.07
Economizer 0.00 0.00 0.00 0.01 0.01 0.01 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.07 0.08 0.08
Filter/Frame Kit 0.01 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.04 0.05 0.05 0.06 0.06 0.07
Electric Heat 0.02 0.03 0.03 0.03 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.01 0.11 0.11 0.12