APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow (CFM)
80% 90% 100% 110% 120%
Capacity Factor
0.96 0.98 1.00 1.02 1.03
PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models AHE18B AHE24B AHE30B AHE36C AHE42D AHE48D AHE60D
Blower - Diameter x Width 10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10 11 x 10
Motor
HP 1/3 HP 1/3 HP 1/3 HP 1/2 HP 1/2 HP 3/4 HP 3/4 HP
Nominal RPM 1050 1050 1050 1050 1050 1050 1050
Voltage 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Amps Full Load (230) 2.8 2.8 2.8 4.1 4.1 6.0 6.0
Filter
1
Type DISPOSABLE OR PERMANENT
Size 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1
Permanent Type Kit 1PF0601BK 1PF0601BK 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK
Shipping / Operating Weight (lbs.) 115/103 120/105 120/105 152/137 168/150 171/153 174/156
1. Field Supplied.
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
FOR
208V
OPERATION MULTIPLY
240V
TABULATED KW & MBH BY
.751
230V 240V .918
220V 240V .840
ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models
Total Motor Amps Minimum Circuit Ampacity
Max. O.C.P.
1
Amps/Type
Minimum Wire
Size A.W.G.
60 Hertz 60 Hertz
208V 230V 208V 230V
AHE MODELS
AHE18B3XH21 2.8 2.8 3.5 3.5 15 14
AHE24B3XH21 2.8 2.8 3.5 3.5 15 14
AHE30B3XH21 2.8 2.8 3.5 3.5 15 14
AHE36C3XH21 4.1 4.1 5.1 5.1 15 14
AHE42D3XH21 4.1 4.1 5.1 5.1 15 14
AHE48D3XH21 6.0 6.0 7.5 7.5 15 14
AHE60D3XH21 6.0 6.0 7.5 7.5 15 14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
* May be 0 (no Circuit Breaker) or 1 (with Circuit Breaker).