York AHE18 THRU 60' Air Conditioner User Manual


 
12 Johnson Controls Unitary Products
680210-YTG-B-0311
AIR FLOW
AIR FLOW DATA - 60 Hz MODELS - 208 VOLT
Models
Blower
Motor Speed
CFM
1
@ External Static Pressure - IWC
1. Dry coil conditions only, tested without filters.
Air handler units are CSA listed to UL 1995/CSA C22.2 236-05 up to 0.30" w.c. external static pressure, including air filter, wet coil, and largest kW size heater, unless
otherwise noted.
Operation not recommended in shaded areas.
0.10 0.20 0.30 0.40 0.50 0.60 0.70
208 Volt
AHE18B3XH21
High #5
1074 1029 999 954 911 865 812
Med High #4
895 846 802 759 701 630 526
Med #3
663 610 556 482 334 219 173
Med Low #2
630 466 346 196 170 67 23
Low #1
630 466 346 196 170 67 23
AHE24B3XH21
High #5
1147 1107 1076 1040 992 942 861
Med High #4
1009 974 941 903 859 811 762
Med #3
826 785 744 690 639 566 501
Med Low #2
654 590 556 479 419 307 251
Low #1
580 491 425 317 224 189 73
AHE30B3XH21
High #5
1147 1107 1076 1040 992 942 861
Med High #4
1009 974 941 903 859 811 762
Med #3
826 785 744 690 639 566 501
Med Low #2
654 590 556 479 419 307 251
Low #1
580 491 425 317 224 189 73
AHE36C3XH21
High #5
1473 1417 1361 1304 1241 1171 1109
Med High #4
1257 1204 1138 1076 1000 928 856
Med #3
1069 997 912 831 772 697 617
Med Low #2
994 800 705 621 554 488 432
Low #1
904 692 411 329 256 152 NA
AHE42D3XH21
High #5
1619 1577 1531 1484 1428 1372 1307
Med High #4
1434 1391 1346 1292 1235 1164 1054
Med #3
1243 1192 1135 1073 978 882 778
Med Low #2
1141 1027 952 842 724 572 559
Low #1
1025 851 465 418 253 208 123
AHE48D3XH21
High #5
1847 1812 1775 1725 1684 1645 1600
Med High #4
1675 1640 1597 1561 1522 1479 1421
Med #3
1436 1394 1349 1301 1246 1182 1095
Med Low #2
1250 1211 1157 1100 1013 924 854
Low #1
1151 1029 965 857 779 720 639
AHE60D3XH21
High #5
2083 2042 2002 1959 1921 1875 1829
Med High #4
1893 1856 1815 1776 1728 1688 1639
Med #3
1642 1609 1564 1512 1467 1416 1340
Med Low #2
1443 1401 1360 1307 1242 1160 1062
Low #1
1259 1198 1140 1067 972 900 797