York 292443-XTG-D-0508 Air Conditioner User Manual


 
292443-XTG-D-0508
14 Johnson Controls Unitary Products
FIGURE 3 - TYPICAL FIELD CONTROL WIRING DIAGRAM
TABLE 10: ADDITIONAL STATIC PRESSURE RESISTANCE 2-1/2 - 3-1/2 TON (DNA030 - 042)
1
DESCRIPTION
RESISTANCE, IWG
CFM
500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000
WET EVAPORATOR COIL .01 .01 .01 .02 .03 .04 .05 .06 .07 .08 .09 .09 - - - -
ECONOMIZER
2
.00 .00 .00 .01 .01 .01 .01 .02 .03 .04 .05 .06 - - - -
FILTER FRAME KIT .01 .02 .04 .06 .08 .10 .13 .16 .17 .18 .19 .20 - - - -
1. Deduct these resistance values from the available external static pressure shown in Tables 8 and 9.
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air
duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 11: ADDITIONAL STATIC PRESSURE RESISTANCE 4 - 5 TON (DNA048 - 060)
1
DESCRIPTION
RESISTANCE, IWG
CFM
500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000
WET EVAPORATOR COIL ----- - - .03.04.05.06.07.07.08.09.09
ECONOMIZER
2
----- - - .02.02.03.03.04.04.04.05.05
FILTER FRAME KIT ----- - - .04.05.05.06.07.08.09.10.11
1. Deduct these resistance values from the available external static pressure shown in Table 8 and 9.
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct
system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.
R
G
W
R
G
C
YY
W
C
PROGRAMMABLE
THERMOSTAT ONLY
**
*
*=Minimumwiresizeof18AWG
wire should be used for all
field installed 24 volt wire.
THERMOSTAT
UNIT TERMINAL STRIP
NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.
24 VOLT
TRANSFORMER