York 292443-XTG-D-0508 Air Conditioner User Manual


 
292443-XTG-D-0508
12 Johnson Controls Unitary Products
TABLE 7: DNA060 COOLING CAPACITIES - 5 TON
TEMPERATURE
OF AIR ON
CONDENSER COIL
AIR ON EVAPORATOR COIL
1,500 CFM 1,750 CFM 2,000 CFM 2,250 CFM 2,500 CFM
WB °F WB °F WB °F WB °F WB °F
72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57
85 °F
NET CAP.
MBH
60.3 56.2 52.0 51.1 62.4 58.1 53.8 52.9 64.4 60.0 55.5 54.6 65.4 60.9 56.4 55.5 66.5 61.8 57.3 56.3
TOTAL POWER
INPUT kW
5.67 5.58 5.48 5.50 5.80 5.71 5.61 5.63 5.93 5.83 5.73 5.75 6.11 6.01 5.91 5.93 6.30 6.20 6.09 6.11
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 39.5 47.7 52.0 51.1 43.5 52.3 53.8 52.9 47.5 56.9 55.5 54.6 50.9 59.4 56.4 55.5 54.3 61.8 57.3 56.3
83 35.2 43.4 50.6 50.9 38.4 47.2 53.1 52.7 41.6 51.0
55.5 54.6 44.3 54.1 56.4 55.5 46.9 57.2 57.3 56.3
80 31.0 39.1 46.4 46.6 33.4 42.2 50.0 50.2 35.8 45.2 53.6 53.9 37.6 47.5 55.4 55.1 39.4 49.8
57.3 56.3
77 26.7 34.8 42.1 42.3 28.3 37.1 44.9 45.2 30.0 39.4 47.8 48.1 31.0 40.9 48.8 48.5 32.0 42.3 49.8 48.9
74 22.4 30.5 37.8 38.0 23.3 32.0 39.9 40.1 24.2 33.6 42.0 42.2 24.3 34.2 42.2 41.8 24.5 34.9 42.4 41.4
71 - 26.3 33.5 33.8 - 27.0 34.8 35.1 - 27.7 36.1 36.4 - 27.6 35.5 35.2 17.1 27.4 34.9 34.0
68 - 22.0 29.3 29.5 - 21.9 29.8 30.0 - 21.9 30.3 30.6 - 20.9 28.9 28.5 9.6 20.0 27.5 26.5
95 °F
NET CAP.
MBH
57.6 53.0 49.0 48.5 59.5 54.7 50.7 50.1 61.5 56.5 52.3 51.7 62.4 57.3 53.1 52.4 63.3 58.1 53.9 53.2
TOTAL POWER
INPUT kW
6.14 6.11 5.96 6.01 6.30 6.27 6.11 6.16 6.45 6.42 6.26 6.32 6.62 6.59 6.43 6.49 6.80 6.76 6.60 6.65
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 37.6 46.8 49.0 48.5 41.5 51.4 50.7 50.1 45.3 56.0 52.3 51.7 48.6 57.1 53.1 52.4 51.8 58.1 53.9 53.2
83 33.3 42.5 48.6 48.2 36.4 46.4 50.5 50.0 39.5 50.2
52.3 51.7 41.9 53.1 53.1 52.4 44.4 56.1 53.9 53.2
80 29.1 38.3 44.4 43.9 31.4 41.3 47.9 47.4 33.7 44.3 51.4 50.9 35.3 46.5 52.6 52.1 36.9 48.6
53.9 53.2
77 24.8 34.0 40.1 39.7 26.3 36.2 42.8 42.4 27.8 38.5 45.5 45.1 28.7 39.8 46.0 45.4 29.5 41.2 46.4 45.7
74 20.5 29.7 35.8 35.4 21.3 31.2 37.8 37.3 22.0 32.7 39.7 39.2 22.0 33.2 39.3 38.8 22.0 33.7 38.9 38.3
71 - 25.4 31.5 31.1 - 26.1 32.7 32.3 - 26.8 33.9 33.4 - 26.6 32.7 32.1 - 26.3 31.5 30.8
68 - 21.2 27.2 26.8 - 21.1 27.6 27.2 - 21.0 28.0 27.6 - 19.9 26.0 25.5 - 18.8 24.0 23.4
105 °F
NET CAP.
MBH
53.0 48.8 45.0 42.7 55.0 50.7 46.8 44.3 57.1 52.5 48.5 45.9 57.6 53.1 49.0 46.4 58.2 53.6 49.5 46.9
TOTAL POWER
INPUT kW
6.85 6.74 6.64 6.64 6.99 6.88 6.78 6.78 7.14 7.03 6.93 6.92 7.34 7.22 7.12 7.12 7.54 7.42 7.31 7.31
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 36.1 45.1 45.0 42.7 39.9 48.7 46.8 44.3 43.7 52.3 48.5 45.9 46.9 53.0 49.0 46.4 50.1 53.6 49.5 46.9
83 31.8 40.8 44.8 42.6 34.9 44.6 46.7 44.2 37.9 48.4
48.5 45.9 40.3 50.5 49.0 46.4 42.6 52.6 49.5 46.9
80 27.6 36.5 41.5 39.4 29.8 39.5 44.9 42.6 32.1 42.5 48.3 45.8 33.6 44.6 48.9 46.3 35.2 46.6
49.5 46.9
77 23.3 32.2 37.2 35.1 24.8 34.5 39.8 37.5 26.3 36.7 42.4 40.0 27.0 37.9 42.2 39.7 27.7 39.2 42.0 39.4
74 19.0 28.0 32.9 30.8 19.7 29.4 34.8 32.5 20.4 30.9 36.6 34.2 20.3 31.3 35.6 33.1 20.3 31.7 34.6 32.0
71 - 23.7 28.6 26.5 - 24.4 29.7 27.4 - 25.0 30.8 28.3 - 24.6 29.0 26.4 - 24.2 27.1 24.5
68 - 19.4 24.4 22.3 - 19.3 24.6 22.4 - 19.2 24.9 22.5 - 18.0 22.3 19.8 - 16.8 19.7 17.1
115 °F
NET CAP.
MBH
48.4 44.7 41.0 36.9 50.5 46.6 42.8 38.5 52.6 48.6 44.6 40.1 52.9 48.8 44.9 40.3 53.2 49.1 45.1 40.5
TOTAL POWER
INPUT kW
7.56 7.37 7.33 7.27 7.69 7.50 7.46 7.40 7.82 7.63 7.59 7.53 8.05 7.85 7.81 7.75 8.28 8.08 8.03 7.97
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 34.6 43.3 41.0 36.9 38.4 45.9 42.8 38.5 42.2 48.6 44.6 40.1 45.2 48.8 44.9 40.3 48.3 49.1 45.1 40.5
83 30.3 39.1
41.0 36.9 33.3 42.8 42.8 38.5 36.3 46.5 44.6 40.1 38.6 47.8 44.9 40.3 40.8 49.1 45.1 40.5
80 26.1 34.8 38.6 34.8 28.3 37.7 41.9 37.8 30.5 40.7 45.2 40.7 31.9 42.6 45.1 40.6 33.4 44.6
45.1 40.5
77 21.8 30.5 34.3 30.5 23.2 32.7 36.8 32.7 24.7 34.9 39.3 34.9 25.3 36.0 38.5 34.0 25.9 37.1 37.7 33.1
74 17.5 26.2 30.0 26.3 18.2 27.6 31.8 27.7 18.8 29.0 33.5 29.1 18.7 29.4 31.9 27.4 18.5 29.7 30.2 25.6
71 - 22.0 25.8 22.0 - 22.6 26.7 22.6 - 23.2 27.7 23.2 - 22.7 25.2 20.7 - 22.2 22.8 18.2
68 - 17.7 21.5 17.7 - 17.5 21.7 17.6 - 17.4 21.8 17.4 - 16.1 18.6 14.1 - 14.8 15.3 10.7
125 °F
NET CAP.
MBH
43.8 40.5 37.1 31.1 46.0 42.6 38.9 32.7 48.2 44.6 40.7 34.3 48.2 44.6 40.8 34.2 48.2 44.6 40.8 34.2
TOTAL POWER
INPUT kW
8.30 8.00 8.00 7.90 8.40 8.10 8.10 8.00 8.50 8.20 8.20 8.10 8.80 8.50 8.50 8.40 9.00 8.70 8.70 8.60
Sensible Capacity
MBH
1
Entering Dry
Bulb °F
86 33.1 41.6 37.1 31.1 36.8 43.2 38.9 32.7 40.6 44.8 40.7 34.3 43.5 44.7 40.8 34.2 46.5 44.6 40.8 34.2
83 28.8 37.3 37.3 31.2 31.8 41.0 39.0
32.7 34.7 44.7 40.7 34.3 36.9 45.2 40.8 34.2 39.1 45.6 40.8 34.2
80 24.5 33.0 35.7 30.2 26.7 36.0 38.9 32.9 28.9 38.9 42.0 35.6 30.3 40.7 41.4 34.9 31.6 42.5
40.8 34.2
77 20.3 28.8 31.4 26.0 21.7 30.9 33.8 27.9 23.1 33.1 36.2 29.8 23.6 34.1 34.8 28.3 24.2 35.1 33.3 26.8
74 16.0 24.5 27.1 21.7 16.6 25.9 28.8 22.8 17.2 27.2 30.4 24.0 17.0 27.4 28.1 21.6 16.7 27.6 25.9 19.3
71 - 20.2 22.9 17.4 - 20.8 23.7 17.8 - 21.4 24.6 18.2 - 20.8 21.5 15.0 - 20.2 18.4 11.9
68 - 15.9 18.6 13.1 - 15.8 18.7 12.7 - 15.6 18.7 12.3 - 14.2 14.8 8.2 - 12.7 10.9 4.4
1. These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY