11
PROGRAMMINGPROGRAMMING
PROGRAMMINGPROGRAMMING
PROGRAMMING
Wired Remote Temperature SensingWired Remote Temperature Sensing
Wired Remote Temperature SensingWired Remote Temperature Sensing
Wired Remote Temperature Sensing
One remote temperature sensor can be installed indoor or
outdoor and connected to the thermostat by a maximum
cable length of 100 meters (300 ft). Three terminals, +, S & -
are provided on the terminal block to connect to the White-
Rodgers standard wired remote sensor. This sensor will be
read by the thermostat only when 24VAC is present.
When used as indoor sensor, the readings can be weighted
with the local sensor for specific program periods. User can
enable or disable the remote sensor in the installer configu-
ration mode and also the outdoor temperature can be
selected to show on the display.
Once in the installer configuration mode, momentarily press
the
or touch key until display indicates
Remote Remote
Remote Remote
Remote (at the
top left of the LCD) and OFF (default – in clock digits).
Pressing
or touch key will toggle the operation and
display from
Remote Remote
Remote Remote
Remote OFF to
Remote Remote
Remote Remote
Remote On.
When
Remote Remote
Remote Remote
Remote On is selected, press
key for the display to
indicate Remote In (for indoor remote).
The
or keys will toggle the operation and display from
Remote InRemote In
Remote InRemote In
Remote In to
Outdoor RemoteOutdoor Remote
Outdoor RemoteOutdoor Remote
Outdoor Remote.
When any remote is selected the temperature will display in
the clock digits for one second alternating with the current
time for three seconds when in
Run ScheduleRun Schedule
Run ScheduleRun Schedule
Run Schedule mode.
Outdoor RemoteOutdoor Remote
Outdoor RemoteOutdoor Remote
Outdoor Remote will indicate at the top left of display for
outdoor remote reading.
Only
Remote Remote
Remote Remote
Remote will show at top left for indoor remote reading.
(
o
F or
o
C will not indicate with remote temperature readings).
Sensing Range:
Outdoor temperature range is -40 to 140
o
F
Indoor temperature range is 32
o
F to 99
o
F
Weight of Remote Reading:Weight of Remote Reading:
Weight of Remote Reading:Weight of Remote Reading:
Weight of Remote Reading:
When in view schedule mode the weight of the indoor remote
sensor will be shown in the left actual temperature digits
designated as A2 (default for average weight), H4 (high
weight) or L1 (low weight). The period (Morning, Day,
Evening, Night) will also be shown to the right of the weight
value in the actual temperature digits.
When in view schedule mode, press
and keys at the
the same time to sequence the indoor remote temperature
sensor weight from A2 to H4 to L1 and back to A2 for each of
the program period times for each day. (The H4 weight is
twice the weight of A2 and A2 is twice the weight of L1).
When
Remote In Remote In
Remote In Remote In
Remote In is selected (with
Remote Remote
Remote Remote
Remote selected to
OnOn
OnOn
On),
press
key for the display to indicate the status of the local
sensor
LS OnLS On
LS OnLS On
LS On (default for thermostat local sensor opera-
tional). The
and keys will toggle the function and
display from
LS LS
LS LS
LS (shown in actual temperature digits) and
OnOn
OnOn
On
(shown in clock digits) to
LS OFF LS OFF
LS OFF LS OFF
LS OFF to designate the local
sensor is disabled.
The local sensor may be disabled only if the indoor remote
sensor is enabled and functional.
If the indoor remote sensor is disabled or not functional, the
local sensor will automatically enable and display in the run
schedule mode.
The actual temperature displayed in the run mode is the
mathematical weighted sum of the two temperature sensors
– local and indoor remote.
(Outdoor remote sensor is not used for this computation).
If the remote sensor is absent or not enabled then the actual
temperature will be as measured by the local sensor.