White Rodgers 1F95-0671 Thermostat User Manual


 
7
INSTALLER/CONFIGURATION MENU
21 20 18 MENU dS (On) Off Selects Automatic Daylight Saving Time option
22 21 19 MENU (OFF)
Keypad Lockout
L, P, Limit Selects one of 3 Keypad Lockout confi gurations
L - Total Keypad Lockout
P - Partial Keypad Lockout
(Up and Keys still work)
Limit - Limited Temperature Range
MENU (000)
Keypad Lockout
1-999 Selects personal lockout code. 000 is NOT A
VALID CODE.
23 22 20 MENU L Heat
(99)
L 62 to L 98 Select Limited HEAT Range Temperature
24 23 21 MENU L Cool
(45)
L 46 to L 82 Select Limited COOL Range Temperature
25 24 MENU CO
(05)
06-50 Selects outdoor Compressor OFF temperature
(Balance Point temperature). 05 disables fea-
ture. Outdoor Remote required
MENU (dF) EA Selects between dF (dual Fuel) or EA (Electric
Aux) only available if CO is greater than 05
MENU Cd
(60)
Selects Compressor delay OFF time in seconds
(only if dF is selected)
26 25 MENU AO
(80)
Selects AO (Auxiliary OFF) temperature. Fea-
ture disabled if 80 is selected. Outdoor Remote
required
27 26 22 MENU Change Filter (OFF) On Selects Filter Change-out Indicator On or OFF.
MENU Change Filter (200 h) 25-1975 h Change Filter time in 25 hour increments. This
menu only appears if On is selected in above.
28 27 23 MENU (OFF)
Change UV Lamp
On Selects UV Lamp
Timer: On/OFF
MENU (350)
Change UV Lamp
25-1975 Selects number of Days between
changing UV Lamp
29 28 24 MENU Cool On (o) Heat On (b) Selects operation of the reversing valve terminal
(O/B) output as an O or B terminal
30 29 27 MENU RUN SCHED Returns to Normal Operation
1) This control can be confi gured for:
MS 2 – Multi-Stage System (no heat pump)
HP 1 – Heat Pump with one stage of compressor
HP 2 – Heat Pump with two stage compressor or two
compressor system, Gas or Electric backup
SS 1 – Single Stage System
2) GAS or Electric (ELE) fan operation. If the heating system
requires the thermostat to energize the fan, select ELE.
Select GAS if the heating system energizes the fan on a
call for heat.
3) Select Cool Savings™ value – Selects the amount of
adjustment for the Cool Savings™ feature in Cool mode
with 1 (1°) being the least amount of adjustment and 6
(6°) being the most amount of adjustment. Default value
is 3. Cool Savings is an optional energy saving feature that
can reduce your cooling costs. It is based on the principal
that lower indoor humidity makes a slightly higher tem-
perature feel more comfortable. Cool Savings operates
during periods of high demand which normally occur on
the hottest summer days when a cooling system may run
for hours to reach the thermostat setting. Long cooling
run times also lower the indoor humidity. Cool Savings,
very slowly, adjusts the setpoint temperature to make the
setpoint closer to the displayed room temperature, to a
maximum of the number of degrees you select. Adjust-
ing the setpoint temperature over a long cooling run time
allows the system to reach your set temperature and turn
off. The room temperature will actually be higher than the
thermostat displays but the reduction in humidity will allow
comfort at the slightly higher temperature.
To turn this feature on in the Cool mode press Cool
Savings. The display will show “Save” next to the set-
point temperature. When Cool Savings is making adjust-
ments to the room temperature display “Save” will be
fl ashing and the displayed room temperature may vary
within the adjustment range you selected.
If "Save" is not displayed and this feature is OFF, no
change will occur when the cooling system is continuously
running during periods of high demand.
4) Energy Management Recovery: (this step is skipped if
confi gured to be non-programmable).
Energy Management Recovery (E) On enables the ther-
mostat to start heating or cooling early to make the building
temperature reach the program setpoint at the time you
specify. Heating will start approximately 5 minutes early
(15 minutes for heat pump) for every 1° of temperature
required to reach setpoint.
Example: E On is selected and your heating is pro-
grammed to 65° at night and 70° at 7 AM. If the building
temperature is 65°, the difference between 65° and 70° is
5°. Allowing 5 minutes per degree, the thermostat setpoint
will change to 70° at 6:35 AM. Cooling allows approxi-
mately 15 minutes per degree, because it takes longer to
reach set temperature.