White Rodgers 1F80-71 Thermostat User Manual


 
4
CHECK THERMOSTAT OPERATION
If at any time during testing, your system does not operate
properly, contact a qualified serviceperson.
Fan Operation
1. Turn on power to the system.
2. Press SYSTEM button until the system is OFF.
3. Move FAN switch to ON. The blower should begin to operate.
4. Move FAN switch to AUTO position. The blower should stop
within a short period of time.
Heating System
1. Press SYSTEM button until HEAT is displayed. If the heating
system has a standing pilot, be sure to light it.
2. Press
to adjust thermostat setting above room tempera-
ture. The heating system should begin to operate.
3. Press to adjust temperature setting below room tem-
perature. The heating system should stop operating.
Cooling System
This thermostat has a built-in short-term (5-minute) time delay.
This feature is activated after the compressor shuts down and
the setpoint is changed within the 5-minute period. During this
5-minute period, COOL will flash on the display indicating that
the thermostat has locked out the compressor to allow head
pressure to stabilize. This thermostat does not sense AC power
loss and therefore does not activate the short term compressor
protection feature when power is restored.
To prevent compressor and/or property damage, if the
outdoor temperature is below 50°F, DO NOT operate
the cooling system.
1. Press SYSTEM button until COOL is displayed.
2. Press
to adjust thermostat setting below room tempera-
ture. The blower should come on immediately on high speed,
followed by cold air circulation
3. Press to adjust temperature setting above room tem-
perature. The cooling system should stop operating.
NOTE
CAUTION
!
LOCKOUT BYPASS OPTION
FOR QUALIFIED SERVICE TECHNICIANS’ USE
ONLY. OPERATORS SHOULD NOT USE THIS FEA-
TURE DUE TO POSSIBILITY OF EQUIPMENT OR
PROPERTY DAMAGE, OR PERSONAL INJURY.
COMPRESSOR SHORT TERM
CYCLE PROTECTION
This thermostat has a built-in short term (5-minute)
time delay. During this 5-minute period, the thermo-
stat will lock out the compressor to allow head pres-
sure to stabilize. If you want to override this feature
while testing thermostat operation, simply press
and buttons at the same time.
DO NOT USE THE LOCKOUT BYPASS OPTION
UNLESS THE COMPRESSOR OIL HEATERS HAVE
BEEN OPERATIONAL FOR 6 HOURS AND THE
SYSTEM HAS NOT BEEN OPERATIONAL FOR AT
LEAST 5 MINUTES.