Whirlpool AS12 Air Conditioner User Manual


 
(1). Unscrew and remove caps from 2 and 3-way valves.
(4). Start vacuum pump for 10-15 minutes until reaching a vacuum of 10 mm Hg absolutes.
(6). Open 2-way valve 1/4 turn then close it after 10 seconds. Check tightness of all joints using liquid
soap or an electronic leak detector.
(7). Turn 2 and 3-way valves stem to fully the valves. Disconnect vacuum pump flexible hose.
(8). Replace and tighten all valve caps.
(5). With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop
vacuum pump.
(2). Unscrew and remove cap from service valve.
(3). Connect vacuum pump flexible hose to the service valve.
How to Purge Air Tubes:
Please read this manual before installing and using it.
Only the air conditioner can be connected to the power line.
Refer to the rating plate of the equipment for power consumption details.
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or
similarly qualified person in order to avoid a hazard.
In order to ensure the suitability of the equipment for connection, the user should consult with the
supply authority, if necessary, that the service current capacity at the interface point is sufficient
for the equipment.
The power connection for the air conditioner has to be done at the main power distribution which has
to be of a low impedance.
Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner.
Testing run the air conditioner after finishing installation, and record details of operation.
Type of fuse used on indoor unit controller is 50T, with rating 2.5A,AC250V.
The fuse for the whole unit is to be provided by the user according to the current at maximum power
Input or use other over-current protective device instead.
22
Installation instructions
Notes