3398
4
GB
APPLICATION FIELD WIRING
Oil Valve
Capacitor
GREEN
BLUE
BLACK
BLACK
WHITE
BLUE
M
BROWN
AL 1009-1
Burner Fan-Off
Ti mer
6
12
8
N
1
11
9
3
2
7
Control Box
530 SE/C
YELLOW
BLUE
RED
GREY
L
WHITE
RED
BLACK
WGRB
WHITE
RED
BROWN
Ground
FACTORY WIRED
SUB BASE
LIMIT
Switches
SAFETY
Switches
Fuse 15 A
L1L2
Earth
Ground
WH ITE
GREEN
BLACK
RED
FIELD
WIRING
Motor
4
AIR PR
E
SSURE
SWITCH
10
BLUE
BLUE
BLUE
REMOTE SENSING OF SAFETY LOCKOUT
The SAFETY SWITCH in the 530SE CONTROL BOX is equipped with a contact allowing remote sensing of burner
lockout. The electrical connection is made at terminal 4 (
•
) on the SUB-BASE.
Should lockout occur the 530SE CONTROL BOX will supply a power source of 120Vac to the connection terminal.
The maximum allowable current draw on this terminal (4) is 1 Amp.
WARNING:
If a neutral or ground lead is attached to this terminal, the CONTROL BOX on the burner will be damaged
should lockout occur.
D8173