Weil-McLain 800058000-Brn-PO Rie F5 Burner User Manual


 
3223
3
GB
INITIAL SET-UP
A) Remove burner and air tube from cartons. Check parts list (inside cover) to ensure all parts are present.
B) Remove burner cover by loosing the three screws securing it. Remove control box and air tube cover.
C) Remove drawer assembly from air tube, insert nozzle and set Turbulator adjustment for specific input required, then
set aside.
D) Mount air tube to burner chassis.
ASSEMBLY OF AIR TUBE TO
BURNER CHASSIS
The air tube and drawer assembly are
shipped in a carton separate from the burner
chassis. Choose the proper air tube length to
obtain the tube insertion for the specific in-
stallation.
A) Remove the AIR TUBE and BURNER
CHASSIS from their respective cartons.
B) Remove the DRAWER ASSEMBLY (1)
from inside the AIR TUBE by loosening
the screw (2). Carefully pull the DRAWER ASSEMBLY out of the AIR TUBE, install the required nozzle (see page 8)
and set aside.
C) Remove the two BOLTS (3) from FRONT PLATE (4) of the BURNER CHASSIS. Align the two holes on the AIR
TUBE HOLDING PATE (5) with the two holes on the BURNER CHASSIS FRONT PLATE with the BOLTS (3) re-
moved. Replace the BOLTS and fingers tighten only. Re-install DRAWER ASSEMBLY into AIR TUBE. Tighten
SCREW (2) securely.
D) Tighten the two bolts (3) securely.
MOUNTING THE BURNER TO THE BOILER OR FURNACE
There are three possible methods to mount the burner, depending on the individual application. These are:
1) Universal flange bolted to Boiler/Furnace unit.
2) Semi-flange collar bolted to Boiler/Furnace unit.
3) Universal flange mounted to optional Pedestal mount, where flange mounting direct to appliance is not possible.
Pedestal kit must be ordered separately.
METHOD 1 – UNIVERSAL MOUNTING FLANGE
S7462
S7461
A
B
A
B
DRY BASE
BOILER
D6013
D6014
COMBUSTION
CHAMBER