United States Stove B2045L Gas Heater User Manual


 
1010
1010
10
GAS CONNECTIONGAS CONNECTION
GAS CONNECTIONGAS CONNECTION
GAS CONNECTION
GAS PRESSURE CHECKGAS PRESSURE CHECK
GAS PRESSURE CHECKGAS PRESSURE CHECK
GAS PRESSURE CHECK
FIGURE 6. Rear View of 2045 Vent-Free Gas HeaterFIGURE 6. Rear View of 2045 Vent-Free Gas Heater
FIGURE 6. Rear View of 2045 Vent-Free Gas HeaterFIGURE 6. Rear View of 2045 Vent-Free Gas Heater
FIGURE 6. Rear View of 2045 Vent-Free Gas Heater
The gas inlet connection is 3/8" NPT, made at
the side of the main control through the area at
the rear of the pedestal.
Test all gas joints from the gas meter to the
heater for leaks using soap and water solution
after completing connection. DO NOT USE
AN OPEN FLAME.
The heater regulator controls the burner pressure which should be checked at the pressure test point located on the
front of the main control and is accessible through the front of the heater. (see FIGURE 6).
The pressure should be checked with the heater burning and the control set to high (HI).
The pressure regulator is preset and locked to avoid tampering. If the pressure is not as specified in Product
Specifications (Page 5), contact your dealer and replace the regulator.
FIGURE 7. Pressure Test Point LocationFIGURE 7. Pressure Test Point Location
FIGURE 7. Pressure Test Point LocationFIGURE 7. Pressure Test Point Location
FIGURE 7. Pressure Test Point Location
Gas Inlet Connection (3/8" NPT)