Twin-Star International 33EB304GRS Indoor Fireplace User Manual


 
Framing Specications: Figure 1
This replace is a zero clearance design. No
combustibles can be placed on the top
surface of the replace. Combustibles may
be installed to the edge of the unit.
For 120 volt installations use two conductor,
non-metallic sheath cable with ground wire
(3 wires total) for the incoming power supply
on replace inserts. Use the appropriate wire
to meet local and national electrical codes for
rated power consumption.
For 208/240 volt installations use three
conductor, non-metallic sheath cable with
ground wire (4 wires total) for the incoming
power supply on replace inserts. Use the
appropriate wire to meet local and national
electrical codes for rated power consumption.
MODEL A B C D E F G H I J K L M
33EB304AAS 15.0” 33.0” 29” 28.5” 23.0” 32.8” 29.6” 18.25” 23.6” 14.3” 48.0” 28.0” 28.0”
33EB364GRS 16.0” 39.0” 33” 32.7” 27.2” 38.7” 36.0” 22.0” 27.6” 15.3” 55.0” 34.0” 34.0”
D
E
F
G
H
I
J
L
K
M
Four mounting anges on the sides of the unit
are provided to facilitate installation.
Insulation and vapor barrier should be placed
a minimum of 2 inches from the unit.
Two conductor, non-metallic sheath cable with
ground wire (3 wires total) is recommended
for installation of a wall mounted thermostat
for use on replace inserts.
Recommended Wire and
Fusing Requirements
Use appropriate wire to meet local and
national electrical codes for rated power con-
sumption. All wire gauges should be
12 gauge with a dedicated 15 amp breaker.
Section 2: Recommended Power Supply Wire Specications
Section 1: Framing
E-3