Trane XT302C Thermostat User Manual


 
XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT
7
69-1213—1 (T8624)
Pub. No. 18-HD25D7-5
Table 3. Installer Setup Options for the XT302C (continued).
M12951
Set Current
Day/Time
Mon
PM
Set Day/Time
Time
Set Program
SystemFilter Fan
Run
Program
Hold Temp
Set Current
Day/Time
Wake
Leave
Return Sleep
Day
Heat/Cool
Settings
Daylight
Time
Copy
IMPORTANT
Review the settings to confirm that they match the
system. Press Run Program to exit the Installer
Setup. The thermostat saves the Installer Setup
changes and initiates a reset in order to operate
using the new settings.
NOTE: For initial installations only, set the current day and
time following the setup reset.
Setting Current Day and Time
1. Press Set Current Day/Time.
NOTE: On initial power up or after an extended power loss,
1:00 pm flashes on the display until a key is pressed.
Press Time
or
Press Increase or Decrease to change setting
Installer
Factory Setting Other Choices
Actual
Select
Setup Number
Display Description Display Description
Setting
Minimum On
Time (Cool)
33 10 10-minute minimum on
time for compressor
0 thru 15 Minimum number of minutes
(0 thru 15) the compressor
will be on during call for
cool
Temperature
range stops in
heating
34 85 Highest setpoint
heating can be set to
55 to 85 Temperature range (1°F
increments) heating
setpoint can be set to
Temperature
range stops in
cooling
35 65 Lowest setpoint
cooling can be set to
65 to 99 Temperature range (1°F
increments) cooling
setpoint can be set to
Temperature
display
adjustment
37 0 No difference
in displayed
temperature and
actual room
temperature
3, 2, 1, -1,
-2, or
-3
3—Display adjusts to 3°F
higher than actual room
temperature
2—Display adjusts to 2°F
higher than actual room
temperature
1—Display adjusts to 1°F
higher than actual room
temperature
-1—Display adjusts to 1°F
lower than actual room
temperature
-2—Display adjusts to 2°F
lower than actual room
temperature
-3—Display adjusts to 3°F
lower than actual room
temperature
Minimum Off
Time (Heat)
38 5 5 minute minimum off
time for the
compressor
0 thru 15 Minimum number of minutes
(0 thru 15) the compressor
will be off between calls for
heat
Minimum Off
Time (Cool)
39 5 5 minute minimum off
time for the
compressor
0 thru 15 Minimum number of minutes
(0 thru 15) the compressor
will be off between calls for
cool
Cooling Droop 41 1 Cooling droop
activated
0 No cooling droop
Programming 42
Press Time to
bypass 2–41
and go directly
to setup #42
0 7-day programming 1 or 2 1—24-hour programming
2—No programming