Table PD-24 Auxiliary Electric Heat Capacity
Total
2
Stage 1 Stage 2
Unit
Model No. kW No. Stages kW kW
8.3 2 4.2 4.2
WSC060AT 12.1 2 6.0 6.0
16 2 9.9 6.0
7.5 / 9.0 2 3.75 / 4.5 3.75 / 4.5
WSC060AD 10.9 / 13.0 2 5.45 / 6.5 5.45 / 6.5
14.4 / 17.2 2 8.95 / 10.7 5.45 / 6.5
12.5 1 12.5
WSC072AT 18.8 2 12.5 6.3
25 2 12.5 12.5
11.3 / 13.5 1 11.3 / 13.5 -
WSC072AD 16.9 / 20.2 2 11.3 / 13.5 5.6 / 6.7
22.6 / 26.9 2 11.3 / 13.5 11.3 / 13.5
12.5 1 12.5
WSC090AT 18.8 2 12.5 6.3
25 2 12.5 12.5
11.3 / 13.5 1 11.3 / 13.5 -
WSC090AD 16.9 / 20.2 2 11.3 / 13.5 5.6 / 6.7
22.6 / 26.9 2 11.3 / 13.5 11.3 / 13.5
18.8 2 12.5 6.3
WSC120AT 25 2 12.5 12.5
37.5 2 25.0 12.5
16.9 / 20.2 2 11.3 / 13.8 5.6 / 6.7
WSC120AD 22.6 / 26.9 2 11.3 / 13.9 11.3 / 13.5
33.9 / 40.4 2 11.3 / 13.10 22.5 / 26.9
Notes:
1. Does not include indoor fan power or heat
2. Heaters are rated at 200V, and 380V / 415V. For other than rated voltage, CAP = (Voltage/Rated Voltage)
2
x Rated Cap.
Table PD-24a Auxiliary Electric Heat Capacity
Total
2
Stage 1 Stage 2
Unit
Model No. MBH No. Stages MBH MBH
28 2 14 14
WSC060AT 41 2 20 20
55 2 34 20
26 / 31 2 13 / 16 13 / 16
WSC060AD 38 / 45 2 19 / 23 19 / 23
50 / 59 2 31 / 37 19 / 23
43 1 43 -
WSC072AT 64 2 43 22
85 2 43 43
39 / 47 1 39 / 47 -
WSC072AD 58 / 69 2 39 / 47 20 / 23
78 / 92 2 39 / 47 39 / 47
43 1 43 -
WSC090AT 64 2 43 22
85 2 43 43
39 / 47 1 39 / 47 -
WSC090AD 58 / 69 2 39 / 47 20 / 23
78 / 92 2 39 / 47 39 / 47
64 2 43 22
WSC120AT 85 2 43 43
123 2 85 43
58 / 69 2 39 / 47 20 / 23
WSC120AD 78 / 92 2 39 / 47 39 / 47
116 / 138 2 39 / 47 77 / 92
Notes:
1. Does not include indoor fan power or heat
2. Heaters are rated at 200V, and 380V / 415V. For other than rated voltage, CAP = (Voltage/Rated Voltage)
2
x Rated Cap.