Performance
Data
Table PD-22 - Static Pressure Drops Through Accessories - (Pascals)
Econimizer with Electric Heater
OA/RA Dampers
2
Accessory (kW)
3
Unit Airflow Standard Pleated Filters 100% OA 100% RA 100% OA 100% RA 7-9 10-27 37-40
Model No. (m
3
/h) Filters
1
50 mm (2 inch) Downflow Horizontal
2720 25 37 30 11 30 4 11 13
WSC060AD,T 3400 37 55 46 17 46 6 17 21
4080 55 72 64 26 64 9 25 30
3260 10 17 25 2 15 5 5
WSC072AD,T 4080 15 22 27 5 20 5 8
4890 22 30 33 10 25 10 13
4080 15 22 27 5 20 5 8
WSC090AD,T 5100 25 32 35 12 30 12 16
6120 35 45 52 17 62 20 25
5440 17 25 42 12 35 12 910
WSC120AD,T 6800 27 37 65 17 75 20 14 17
8160 40 50 85 22 87 25 20 26
Notes:
1. Tested with standard filters. The WSC060AD,T has 25 mm (1 inch) standard fiters. The WSC072AD,T - 120AD,T has 50 mm (2 inch) standard filters. The difference in pressure drop
should be considered when utilizing optional 50 mm (2 inch) pleated filters.
2. OA = Outside Air and RA = Return Air
3. Nominal kW ratings at 380 V
Table PD-22a - Static Pressure Drops Through Accessories - (Inches of Water Column)
Econimizer with Electric Heater
OA/RA Dampers
2
Accessory (kW)
3
Unit Airflow Standard Pleated Filters 100% OA 100% RA 100% OA 100% RA 7-9 10-27 37-40
Model No. (CFM) Filters
1
50 mm (2 inch) Downflow Horizontal
1600 0.10 0.15 0.12 0.04 0.12 0.01 0.045 0.053
WSC060AD,T 2000 0.15 0.22 0.18 0.07 0.18 0.02 0.070 0.083
2400 0.22 0.29 0.26 0.10 0.26 0.04 0.100 0.120
1920 0.04 0.07 0.10 0.01 0.06 0.02 0.021
WSC072AD,T 2400 0.06 0.09 0.11 0.02 0.08 0.02 0.034
2880 0.09 0.12 0.13 0.04 0.10 0.04 0.052
2400 0.06 0.09 0.11 0.02 0.08 0.02 0.034
WSC090AD,T 3000 0.10 0.13 0.14 0.05 0.12 0.05 0.063
3600 0.14 0.18 0.21 0.07 0.25 0.08 0.102
3200 0.07 0.10 0.17 0.05 0.14 0.05 0.036 0.042
WSC120AD,T 4000 0.11 0.15 0.26 0.07 0.30 0.08 0.056 0.070
4800 0.16 0.20 0.34 0.09 0.35 0.10 0.081 0.106
Notes:
1. Tested with standard filters. The WSC060AD,T has 25 mm (1 inch) standard fiters. The WSC072AD,T - 120AD,T has 50 mm (2 inch) standard filters. The difference in pressure drop
should be considered when utilizing optional 50 mm (2 inch) pleated filters.
2. OA = Outside Air and RA = Return Air
3. Nominal kW ratings at 380 V
Table PD-23 Electric Heater Voltage Correction
Factors (Apply to Auxiliary Heat
Capacity)
Nominal Distribution Capacity
Voltage Voltage Multipiler
200 200 1.00
380 0.84
415 400 0.93
415 1.00