Constant-Volume Single-
Duct VAV ( VCV 3011)
This is used when a constant volume of
air is required to supply a zone. A
thermostat is still often required to
modulate a reheat coil to maintain
temperature control. The thermostat is
never connected to the “T” port on the
volume regulator. The following
procedure is used to calibrate this type
of unit with a PVR.
Constant-Volume
Single-Duct VAV (VCV 3011)
1. Be sure there is 0 psi at the “T” port.
2. Set LO thermostat adjustment knob to
desired unit cfm.
The unit will now modulate to the
calibrated cfm setting. See Figure 18 for
typical constant volume single-duct
piping diagram.
Figure 18–Typical Constant-Volume Single-Duct Piping Diagram
Tee
(137.9)
20
S
(Reverse-Acting)
T-Stat
Two-Pipe
Remote-Mounted
Electric Heater Terminal Box
(75.8)
11
(86.2)
12.5
14
(96.5)
Stage 1
Stage 2
Stage 3
Airflow
Safety Switch
P.E. Stage Switch(es)
(Normally-Open)
(137.9)
20
S
Flow Ring
Actuator
HI
LO
H L
Regulator
B
M
Volume
T