Trane UX1B060A9361A Furnace User Manual


 
18-CD19D6-32 19
Installer’s Guide
Table 12 - See Figure 27
Direct Vent Terminal Clearances
Canadian Installations US Installations
A=
Clearance above grade, veranda, porch, deck, or
balcony
12 inches (30 cm) 12 inches (30 cm)
B= Clearance to window or door that may be opened
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9
inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/<
50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000
Btuh (15 kw)
C= Clearance to permanently closed window * *
D=
Vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 2 feet (61 cm)
from the center line of the terminal
**
E= Clearance to unventilated soffit * *
F= Clearance to outside corner * *
G-
=
Clearance to inside corner * *
H=
Clearance to each side of center line extended above
meter/regulator assembly
3 feet (91 cm) with a height 15 feet (4.5 m) above the
meter/regulator assembly
*
I= Clearance to service regulator vent outlet 3 feet (91 cm) *
J=
Clearance to nonmechanical air supply inlet to building
or the combustion air inlet to any other appliance
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 9
inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/<
50,000 Btuh (15 kw), 12 inches (30 cm) for appliances > 50,000
Btuh (15 kw)
K= Clearance to a mechanical air supply inlet 6 feet (1.83m) 3 feet (91 cm) above if within 10 feet (3m) horizontally
L=
Clearance above a paved sidewalk or paved driveway
located on public property
7 feet (2.13 m) † *
M-
=
Clearance under veranda, porch, deck, or balcony `12 inches (30 cm) ‡ *
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.
Table 12A - See Figure 27
Non-Direct Vent Terminal Clearances
Canadian Installations US Installations
A=
Clearance above grade, veranda, porch, deck, or
balcony
12 inches (30 cm) 12 inches (30 cm)
B= Clearance to window or door that may be opened
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
4 feet (1.2m) below or to the side of opening; 1 foot (0.3m)
above opening.
C= Clearance to permanently closed window * *
D=
Vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 2 feet (61 cm)
from the center line of the terminal
**
E= Clearance to unventilated soffit * *
F= Clearance to outside corner * *
G= Clearance to inside corner * *
H=
Clearance to each side of center line extended above
meter/regulator assembly
3 feet (91 cm) with a height 15 feet (4.5 m) above the
meter/regulator assembly
*
I= Clearance to service regulator vent outlet 3 feet (91 cm) *
J=
Clearance to nonmechanical air supply inlet to building
or the combustion air inlet to any other appliance
6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12
inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<
100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >
100,000 Btuh (30 kw)
4 feet (1.2 m) below or to side of opening; 1 foot (300 m) above
opening
K= Clearance to a mechanical air supply inlet 6 feet (1.83m) 3 feet (91 cm) above if within 10 feet (3m) horizontally
L=
Clearance above a paved sidewalk or paved driveway
located on public property
7 feet (2.13 m) † 7 feet (2.13 m)
M= Clearance under veranda, porch, deck, or balcony `12 inches (30 cm) ‡ *
Notes:
1. In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.
†. A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.
‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.