Trane TSC060-120 50 Hz Heating System User Manual


 
23
RT-PRC016-EN
Performance
Data
Table PD-10 — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & Low Static Drive 1.50 Nom kW Standard Motor
&
Drive
4080 - - - - - - 701 0.47 750 0.54 794 0.60 834 0.67 873 0.73 909 0.80 945 0.87
4590 - - - - 699 0.53 743 0.59 787 0.66 830 0.74 871 0.82 908 0.89 943 0.96 977 1.04
5100 - - 703 0.61 747 0.68 789 0.74 827 0.82 867 0.90 906 0.98 944 1.06 980 1.15 1013 1.23
5610 713 0.69 755 0.77 797 0.85 836 0.92 873 1.00 908 1.08 944 1.17 980 1.26 1016 1.35 1050 1.45
6120 771 0.88 809 0.96 848 1.06 885 1.14 921 1.22 954 1.30 986 1.39 1019 1.49 1052 1.58 1085 1.69
External Static Pressure (Pascals)
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Motor 1.50 Nom kW Standard Motor
& Drive & Hi Static Drive
4080 980 0.95 1013 1.02 1046 1.10 1076 1.17 1106 1.25
4590 1010 1.11 1043 1.19 1074 1.27 1105 1.36 1134 1.44
5100 1045 1.31 1076 1.39 1105 1.47 1134 1.56 1163 1.65
5610 1081 1.54 1111 1.63 1141 1.72 1168 1.80 1197 1.90
6120 1116 1.79 1148 1.89 1177 1.99 1204 2.08 1232 2.18
2.24 Nom kW Over-Sized Motor
& Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
1.50 Nom kW Standard Motor
& Hi Static Drive
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-10a — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor
&
Low Static Drive 2 HP Standard Motor
&
Drive
2400 - - - - - - 701 0.63 750 0.72 794 0.81 834 0.90 873 0.98 909 1.08 945 1.17
2700 - - - - 699 0.70 743 0.79 787 0.89 830 0.99 871 1.09 908 1.19 943 1.29 977 1.39
3000 - - 703 0.81 747 0.91 789 0.99 827 1.10 867 1.20 906 1.31 944 1.43 980 1.54 1013 1.65
3300 713 0.93 755 1.03 797 1.15 836 1.24 873 1.34 908 1.45 944 1.57 980 1.69 1016 1.82 1050 1.94
3600 771 1.19 809 1.29 848 1.42 885 1.53 921 1.63 954 1.74 986 1.87 1019 1.99 1052 2.13 1085 2.26
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Mtr 2 HP Standard Motor &
& Drive Hi Static Drive
2400 980 1.27 1013 1.37 1046 1.47 1076 1.57 1106 1.68
2700 1010 1.49 1043 1.60 1074 1.71 1105 1.82 1134 1.93
3000 1045 1.76 1076 1.87 1105 1.98 1134 2.09 1163 2.21
3300 1081 2.06 1111 2.18 1141 2.30 1168 2.42 1197 2.55
3600 1116 2.39 1148 2.53 1177 2.66 1204 2.79 1232 2.93
3 HP Over-Sized Mtr & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
2 HP Standard Motor
& Hi Static Drive
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.