Table PD-9a — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive 1-1/2 HP Standard Motor
&
Drive
1920 - - 565 0.31 627 0.39 679 0.45 726 0.52 771 0.60 814 0.69 857 0.77 899 0.85 939 0.93
2160 566 0.35 609 0.41 663 0.48 716 0.57 762 0.64 804 0.72 843 0.80 883 0.90 922 0.99 960 1.08
2400 619 0.47 660 0.54 701 0.60 751 0.69 798 0.78 839 0.87 877 0.95 914 1.04 950 1.14 984 1.24
2640 672 0.61 710 0.68 745 0.76 788 0.83 833 0.93 875 1.04 914 1.13 949 1.22 984 1.31 1016 1.42
2880 726 0.77 762 0.86 795 0.94 828 1.02 869 1.11 911 1.21 950 1.33 986 1.44 1019 1.53 1051 1.63
1-1/2 HP Standard Motor
&
Drive 1-1/2 HP Std Motor & Hi Static Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor
&
Hi Static Drive
1920 978 1.02 1015 1.11 1051 1.20 1086 1.30 1118 1.39
2160 996 1.17 1034 1.27 1069 1.36 1103 1.46 1136 1.56
2400 1020 1.35 1055 1.45 1089 1.55 1122 1.66 1154 1.76
2640 1049 1.53 1081 1.65 1113 1.76 1144 1.87 1176 1.98
2880 1081 1.74 1112 1.86 1141 1.97 1170 2.10 1199 2.22
2 HP Over-Sized Motor
&
High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-9 — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor
&
Low Static Drive 1.12 Nom kW Standard Motor
&
Drive
3260 - - 565 0.23 627 0.29 679 0.34 726 0.39 771 0.45 814 0.51 857 0.57 899 0.63 939 0.70
3670 566 0.26 609 0.31 663 0.36 716 0.42 762 0.48 804 0.54 843 0.60 883 0.67 922 0.74 960 0.81
4080 619 0.35 660 0.40 701 0.45 751 0.51 798 0.59 839 0.65 877 0.71 914 0.78 950 0.85 984 0.93
4490 672 0.45 710 0.51 745 0.56 788 0.62 833 0.69 875 0.77 914 0.85 949 0.91 984 0.98 1016 1.06
4890 726 0.58 762 0.64 795 0.70 828 0.76 869 0.82 911 0.91 950 0.99 986 1.07 1019 1.14 1051 1.22
1.12 Nom kW Standard Motor
&
Drive 1.12 Nom kW Standard Motor
& Hi Static Drive
External Static Pressure (Pascals)
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Hi Static Drive
3260 978 0.76 1015 0.83 1051 0.90 1086 0.97 1118 1.04
3670 996 0.87 1034 0.95 1069 1.02 1103 1.09 1136 1.17
4080 1020 1.00 1055 1.08 1089 1.16 1122 1.23 1154 1.31
4490 1049 1.14 1081 1.23 1113 1.31 1144 1.40 1176 1.48
4890 1081 1.30 1112 1.38 1141 1.47 1170 1.57 1199 1.66
1.50 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.