Table PD-50 Belt Drive Evaporator Fan Performance 8½-Ton THC102A3,A4,AW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 -- -- -- -- 584 0.53 626 0.64 668 0.76 708 0.88 746 1.00 781 1.12 814 1.26 845 1.40
3060 -- -- -- -- 626 0.68 665 0.78 703 0.90 740 1.04 775 1.17 810 1.30 843 1.44 875 1.58
3400 -- -- 628 0.72 669 0.84 706 0.96 741 1.08 775 1.21 809 1.36 841 1.51 873 1.65 904 1.81
3400 641 0.81 677 0.92 713 1.04 749 1.17 781 1.30 813 1.43 845 1.58 875 1.73 905 1.89 935 2.06
4080 693 1.03 726 1.15 758 1.27 792 1.41 824 1.56 854 1.69 883 1.83 912 1.99 940 2.16 968 2.33
2-HP Standard Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:NOTES:
NOTES:NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-50 Continued
External Static Pressure (Inches of Water)
1. 10 1.2 0 1.30 1. 40 1.50 1.60 1.70 1. 80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 874 1.54 904 1.69 930 1.84 958 2.00 983 2.14 1010 2.30 1035 2.46 1060 2.62 1084 2.78 1109 2.95
3060 905 1.73 933 1.89 960 2.05 986 2.20 1010 2.37 1035 2.54 1059 2.71 1083 2.89 1107 3.06 1131 3.24
3400 933 1.96 962 2.11 990 2.27 1016 2.44 1041 2.62 1065 2.79 1089 2.97 1112 3.15 1134 3.34 -- --
3400 964 2.22 992 2.39 1018 2.55 1045 2.72 1071 2.90 1095 3.08 1118 3.26 1141 3.45 -- -- -- --
4080 995 2.51 1023 2.69 1048 2.86 1075 3.05 1100 3.23 1124 3.41 -- -- -- -- -- -- -- --
3-HP Oversized Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
Table PD-51 Belt Drive Evaporator Fan Performance 8½-Ton THC102A3,A4,AW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2720 612 0.60 660 0.71 703 0.81 751 0.95 798 1.09 841 1.23 877 1.36 909 1.48 939 1.60
3060 631 0.72 667 0.80 709 0.91 750 1.03 788 1.15 830 1.29 873 1.45 914 1.62 951 1.77 983 1.92
3400 692 0.96 726 1.05 760 1.15 800 1.29 836 1.42 870 1.56 907 1.71 945 1.88 984 2.06 1020 2.24
3740 754 1.26 786 1.36 815 1.46 850 1.59 886 1.74 918 1.88 949 2.03 980 2.19 1015 2.37 1052 2.57
4080 817 1.61 848 1.72 874 1.83 903 1.95 935 2.10 968 2.26 998 2.42 1026 2.58 1054 2.75 1085 2.94
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:NOTES:
NOTES:NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-51 Continued
External Static Pressure (Inches of Water)
1. 10 1.2 0 1.30 1. 40 1.50 1.60 1.70 1. 80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 967 1.72 994 1.84 1018 1.96 1042 2.07 1066 2.19 1089 2.31 1112 2.43 1134 2.55 1155 2.67 1176 2.79
3080 1012 2.06 1039 2.19 1065 2.32 1090 2.46 1113 2.59 1136 2.73 1158 2.86 1179 2.99 1199 3.12 1220 3.26
3400 1052 2.41 1083 2.58 1109 2.73 1135 2.88 1159 3.04 1183 3.19 1204 3.33
374010862.7711192.9611493.1511783.34—— —— ———————
4080 1117 3.14 1151 3.36 ———————
3-HP Oversized Motor & Drive
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.