Trane RT-PRC005 Fan User Manual


 
30
RT-PRC005-EN
Performance
Data
(6 Ton)
Standard Efficiency
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
Table PD-27 Continued
External Static Pressure (Inches of Water)
1. 10 1.2 0 1.30 1. 40 1.50 1.60 1.70 1. 80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1 HP Standard Motor & Drive 1HP Standard Motor & High Static Drive Kit
(or 2 HP Oversized Motor & Drive)
1920 925 0.95 960 1.03 994 1.11 1026 1.19 1057 1.27 1087 1.36 1116 1.44 1144 1.52 1173 1.61 1200 1.70
2160 944 1. 08 9 78 1.17 1010 1.26 1043 1. 36 1073 1.44 110 4 1.54 1133 1.63 1162 1.7 2 1189 1.81 1216 1.91
2400 964 1.22 998 1.32 1030 1.42 1063 1.53 1092 1.63 1123 1.73 1151 1.83 1179 1.93 1206 2.03 1233 2.13
2640 986 1.39 1019 1.49 1051 1.60 1082 1.71 1112 1.81 1141 1.92 1169 2.03 1198 2.15 1225 2.26
2880 1011 1.58 1043 1.69 1073 1.79 1103 1.90 1133 2.02 1161 2.13 1190 2.26
2 HP Oversized Motor & Drive
Table PD-27 Belt Drive Evaporator Fan Performance 6-Ton TSC072A3,A4,AW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1920 573 0.34 630 0.41 680 0.48 726 0.55 769 0.62 811 0.70 851 0.78 889 0.87
2160 548 0.35 602 0.42 656 0.50 706 0.58 751 0.65 792 0.73 832 0.81 871 0.90 908 0.99
2400 584 0.45 635 0.52 682 0.60 732 0.69 777 0.77 818 0.86 856 0.95 893 1.04 930 1.13
2640 569 0.47 621 0.56 670 0.64 715 0.72 758 0.81 802 0.91 845 1.01 883 1.10 919 1.20 953 1.29
2880 612 0.60 660 0.69 706 0.78 749 0.86 789 0.96 830 1.06 870 1.16 909 1.27 945 1.37 979 1.48
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:NOTES:
NOTES:NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Table PD-28 Belt Drive Evaporator Fan Performance 6-Ton TSC072A3,A4,AW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1920 565 0.31 627 0.39 679 0.45 726 0.52 771 0.60 814 0.69 857 0.77 899 0.85 939 0.93
2160 566 0.35 609 0.41 663 0.48 716 0.57 762 0.64 804 0.72 843 0.80 883 0.90 922 0.99 960 1.08
2400 619 0.47 660 0.54 701 0.60 751 0.69 798 0.78 839 0.87 877 0.95 914 1.04 950 1.14 984 1.24
2640 672 0.61 710 0.68 745 0.76 788 0.83 833 0.93 875 1.04 914 1.13 949 1.22 984 1.31 1016 1.42
2880 726 0.77 762 0.86 795 0.94 828 1.02 869 1.11 911 1.21 950 1.33 986 1.44 1019 1.53 1051 1.63
2-HP Oversized
Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:NOTES:
NOTES:NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop
due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range
of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be
affected.
1-HP Standard Motor
& Field Supplied
Low Static Drive (1)
1HP Standard Motor & High Static Drive
Kit(or 2 HP Oversized Motor & Drive)
Table PD-28 Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard 1-HP Standard Motor & High Static Drive Kit
Motor& Drive (or 2 HP oversized Motor& Drive)
1920 978 1.02 1015 1.11 1051 1.20 1086 1.30 1118 1.39 1150 1.49 1180 1.58 1209 1.68 1236 1.77 1263 1.86
2160 996 1.17 10 34 1.27 1069 1.36 110 3 1.46 1136 1.56 1169 1. 67 119 9 1.77 1229 1. 88 1258 1. 98
2400 1020 1.35 1055 1.45 1089 1.55 1122 1.66 1154 1.76 1186 1.86 1216 1.97 1246 2.08 1276 2.20
2640 1049 1.53 1081 1.65 1113 1.76 1144 1.87 1176 1.98 1207 2.10 1237 2.21
2880 1081 1.74 1112 1.86 1141 1.97 1170 2.10 1199 2.22 ———————
2-HP Oversized Motor & Drive