Trane RT-PRC005 Fan User Manual


 
33
RT-PRC005-EN
(8½ Ton)
Standard Efficiency
Performance
Data
Table PD-33 Belt Drive Evaporator Fan Performance 8½-Ton TSC102A3,A4,AW, AK DownflowAirflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor
Low Static Drive (1) & Drive
2720 613 0.60 655 0.72 695 0.84 733 0.95 769 1.08 802 1.21 833 1.34
3060 611 0.64 650 0.74 688 0.85 725 0.98 761 1.11 796 1.25 828 1.38 861 1.52
3400 612 0.68 651 0.79 689 0.91 724 1.02 759 1.15 792 1.29 825 1.43 856 1.58 887 1.72
3740 622 0.76 659 0.86 693 0.97 729 1.10 764 1.23 795 1.35 826 1.49 857 1.64 887 1.79 916 1.96
4080 671 0.96 706 1.08 738 1.19 770 1.32 804 1.46 834 1.60 864 1.74 892 1.88 920 2.04 948 2.20
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:NOTES:
NOTES:NOTES:
NOTES:
Data includes pressure drop due to stnadard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-33 Continued
External Static Pressure (Inches of Water)
1. 10 1.2 0 1.30 1. 40 1.50 1.60 1.70 1. 80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 863 1.48 892 1.63 920 1.78 946 1.93 973 2.08 999 2.24 1025 2.39 1050 2.55 1073 2.71 1098 2.88
3060 891 1.66 919 1.81 946 1.96 973 2.12 999 2.29 1024 2.46 1048 2.63 1072 2.80 1096 2.98 1119 3.14
3400 917 1.87 946 2.03 974 2.18 1001 2.34 1026 2.52 1051 2.69 1074 2.86 1099 3.05 1121 3.23 1143 3.41
3740 945 2.11 974 2.28 1001 2.44 1028 2.61 1054 2.78 1079 2.96 1103 3.14 1126 3.32
4080 976 2.38 1002 2.56 1029 2.73 1055 2.91 1081 3.09 1105 3.26 1130 3.45
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
Table PD-34 Continued
External Static Pressure (Inches of Water)
1. 10 1.2 0 1.30 1. 40 1.50 1.60 1.70 1. 80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 956 1.67 982 1.79 1008 1.91 1033 2.03 1056 2.14 1079 2.26 1102 2.38 1125 2.50 1146 2.62 1168 2.74
3060 999 1.99 1026 2.12 1052 2.26 1078 2.39 1101 2.52 1124 2.66 1146 2.79 1168 2.92 1188 3.05 1209 3.18
3400 1034 2.32 1067 2.49 1094 2.64 1120 2.79 1145 2.94 1168 3.09 1191 3.24 1213 3.39
3740 1063 2.63 1098 2.84 1129 3.03 1158 3.21 1185 3.39 ———————
4080 1093 2.99 1125 3.19 1157 3.40 ———————
Table PD-34 Belt Drive Evaporator Fan Performance 8½-Ton TSC102A3,A4,AW, AK Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied 2-HP Standard Motor & Drive
Low Static Drive (1)
2720 598 0.57 646 0.67 689 0.78 734 0.90 781 1.04 826 1.18 865 1.31 898 1.44 928 1.56
3060 616 0.69 654 0.77 693 0.86 735 0.98 773 1.10 812 1.23 855 1.39 897 1.55 934 1.70 969 1.85
3400 675 0.92 711 1.01 743 1.10 781 1.22 819 1.36 853 1.49 886 1.62 925 1.79 964 1.97 1000 2.14
3740 735 1.20 770 1.30 799 1.40 830 1.51 865 1.65 899 1.79 930 1.94 960 2.09 994 2.26 1028 2.44
4080 796 1.53 828 1.65 857 1.76 883 1.86 913 1.99 945 2.15 977 2.30 1006 2.47 1034 2.63 1061 2.79
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:NOTES:
NOTES:NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.