Electrical
Data
Table ED-7 — Unit Wiring - High Efficiency - Dehumidification (Hot Gas Reheat) Option
(Downflow Only)
Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity
2
Circuit Breaker
1
Ampacity
2
Circuit Breaker
1
TCD151C3 187-253 59 70 65 80
12½ TCD151C4 414-506 30 35 32 40
TCD151CW 517-633 24 30 26 30
TCD181C3 187-253 71 90 77 100
15 TCD181C4 414-506 36 45 39 50
TCD181CW 517-633 28 35 30 40
TCD241C3 187-253 98 125 105 125
20 TCD241C4 414-506 50 60 53 60
TCD241CW 517-633 39 50 42 50
Notes:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.
(High Efficiency)